SECTION 4
SUPERVISOR CONTROLLER™ USER MANUAL
25
User
X500
150
150
360
Unload
500psi transducer unload pressure
User
Always
150
150
560
Unload
750psi transducer unload pressure
User
Always
10
3
70
Load Delta
Differential pressure from unload pressure
User
Always
15
0
59
Unload Time
Auto mode shut down after unloaded for
this time
User
Always
0
0
30
Drain Interval
Time between drains (Minutes)
User
Always
0
0
10
Drain Time
Duration of drain (Seconds)
User
Always
0
0
59
Restart Time
Auto restart on power up if not 0 (Seconds)
User
Always
0
0
15
Wye Delta
Wye to delta starter transition time
(Seconds)
User
Always
0
0
2
Language
French, German, Italian, Spanish, English
User
Always
0
0
1
Temp Units
Fahrenheit, Celsius
User
Always
0
0
2
Press Units
Pressure units, Psi, Bar, kPa
Seq
Com
Mod
0
0
4
Sequence by
Disabled,Com, Hours, Remote, Slave,
Time Of Day etc.
Seq
Always
0
0
100000
Seq Hrs
Used for Hours sequencing mode
Seq
Always
1
1
16
Com Number
Communications ID number
Seq
Always
1
1
16
Machines
Number of machines in a system
Seq
Always
70
20
185
Low Press
Panic start next machine in sequence
Seq
Always
10
2
59
Recover Time
Keeps multiple machines from starting at
same time (seconds)
Seq
Always
0
0
250
Rotate
Used to force a machine to stop
Table 4-4: Parameters
Type
Enable
Default
Min
Max
Display Text
Comment
Содержание SUPERVISOR CONTROLLER
Страница 8: ...NOTES 6...
Страница 15: ...13 NOTES...
Страница 16: ...SUPERVISOR CONTROLLER USER MANUAL SECTION 2 14 Table 2 1 Supervisor Controller Menu Tree...
Страница 18: ...16 NOTES...
Страница 30: ...28 NOTES...
Страница 31: ...Section 5 29 SUPERVISOR CONTROLLER USER MANUAL WIRING DIAGRAMS...
Страница 49: ...SECTION 6 SUPERVISOR CONTROLLER USER MANUAL 47 VSD FILTER DRAWING V200TS FILTER ELEMENT Figure 6 2 V200TS...
Страница 51: ...NOTES...