SUPERVISOR CONTROLLER™ USER MANUAL
SECTION 6
38
6.6
FAULT AND WARNING
CODES
The Supervisor constantly monitors drive
performance through the serial channel. The
following messages are specifically displayed by the
Supervisor in the event of problems.
Fault
Possible Cause
Solution
VSD Param Lim Fault
Incorrect model, HP or Voltage selected in
Factory & VSD Setup
Make proper selections
VSD Com Error
Communications lost with the VSD
Check connections to the VSD.
Check VSD control power and check
for board faults.
VSD Emergency Stop
(VSD Code 51)
Emergency Stop is pressed
Break in Estop wiring
Clear the package emergency stop.
Check Estop wiring to the drive
input.
VSD Com Fault
(VSD code 53)
Communications problems detected
reported by the VSD
Check connections to the VSD.
Check VSD control power and check
for board faults.
Drive Fault xx
Problem reported by the VSD
Refer to fault codes in table below
Drive fault codes are used for least-likely faults. The Supervisor will display these as "Drive Fault"
with a code number. If a keypad service tool is plugged into the drive, it will display the fault code
and the fault name shown in the first two columns.
Code
Fault
Possible Cause
Solution
1
Overcurrent
The variable speed drive has
detected a high current (>4xIn) in
its output due to:
• sudden heavy load increase
• short in the motor
• short in the cables to the motor
• unsuitable motor
Check loading.
Check motor.
Check cables.
2
Overvoltage
The DC-link voltage has
exceeded its high limit due to:
• too short a deceleration time
• high voltage levels or surges in
the utility supply
Make the deceleration time longer.
Use a chopper and brake resistor.
Correct utility supply voltage (level
is too high).
Add input impedance to limit
surges.
3
Ground Fault
(Earth Fault)
Current sensing indicates that the
sum of motor phase currents is
not zero.
• insulation failure in motor or
motor cables
Remove faults from ungrounded
systems.
Check the motor and motor cables.
5
Charging Switch
The charging switch was open
when the START command was
been given due to:
• faulty operation
• component failure
Reset the fault and restart.
Should the fault re-occur, contact
Sullair service
Содержание SUPERVISOR CONTROLLER
Страница 8: ...NOTES 6...
Страница 15: ...13 NOTES...
Страница 16: ...SUPERVISOR CONTROLLER USER MANUAL SECTION 2 14 Table 2 1 Supervisor Controller Menu Tree...
Страница 18: ...16 NOTES...
Страница 30: ...28 NOTES...
Страница 31: ...Section 5 29 SUPERVISOR CONTROLLER USER MANUAL WIRING DIAGRAMS...
Страница 49: ...SECTION 6 SUPERVISOR CONTROLLER USER MANUAL 47 VSD FILTER DRAWING V200TS FILTER ELEMENT Figure 6 2 V200TS...
Страница 51: ...NOTES...