background image

4.1 MOUNTING OF COMPRESSOR

A suitable foundation or fabricated support must be

established to support the compressor. It should be rigid

enough to keep the compressor frame level and maintain

alignment of the compressor and motor. Tie-down bolts of

sufficient size must be used to provide uniform contact

between the foundation and the compressor frame.

Materials such as rubber or cork can be used to provide

uniform contact between the foundation and compressor

frame.

Piping loads must be eliminated through the use of flex

connectors or other systems which prevent piping

loads from being transmitted to the compressor.

Special consideration should be made to meet

national and local electrical codes for the required

space around and in front of the electrical panel.

Lighting should be provided for future service

requirements.

Accessibility for fork lift trucks, overhead cranes and

maintenance vehicles should be given careful

consideration in order to provide any maintenance

that may be required. Adequate space around the unit

should be provided for access to all components of the

compressor.

Softer surfaces in walls or ceilings will absorb sound

and minimize ambient noise levels. Harder, reflective

surfaces will increase ambient noise levels.

NOTE

Ambient temperatures above 104˚F

(40˚C) require that the high ambient

option is specified for the

compressor.

4.2 VENTILATION AND COOLING

Air-Cooled Compressors

An area with adequate space must be provided for the

compressor and its components. Air-cooled

compressors require a minimum of 3 feet (1 meter)

around the perimeter of the compressor.

The location should be free from standing water and

allow access to clean air that is free from exhaust and

paint fumes, dust, metal filings or caustic chemicals.

Cooling air should be removed from the area in order

to prevent the re-introduction of heated exhaust air

back into the compressor’s cooling system.

Reduced headroom above the compressor will

require that cooling air be either ducted or in some way

deflected away from the compressor. Inadequate

ventilation will result in higher ambient operating

temperatures.

NOTE

Systems that employ both a

conventional reciprocating

compressor and a screw-type axial

compressor must be isolated from

each other by use of a common

receiver tank. Individual airlines from

each compressor should be piped to

the common receiver tank.

NOTE

Shipping straps are painted red in

order to help identify them for

removal. Be sure to remove them prior

to operation of the compressor.

®

SULLAIR

®

Section 4

INSTALLATION

®

SULLAIR

®

1100e, 1500e, 1800e Operator’s Manual and Parts List

31

Содержание 1107e

Страница 1: ...25HP Air Cooled Standard 24 KT PART NUMBER 02250155 844 KEEP FOR FUTURE REFERENCE SULLAIR CORPORATION The information in this document is correct at the time of printing for utility compressor serial...

Страница 2: ...headquarters in Michigan City Indiana Instruction includes discussion of the function and installation of Sullair service parts troubleshooting of the most common problems and actual equipment operat...

Страница 3: ...AR 12 Full Load Mode 50 to 100 PSIG 3 4 to 6 9 BAR 12 Modulating Mode 100 to 110 PSIG 6 9 to 7 6 BAR 12 Unload Mode In Excess of 110 PSIG 7 6 BAR 12 Load No Load Control 12 Automatic Operation 12 Air...

Страница 4: ...ntenance 40 Air Filter Element Replacement 40 Separator Maintenance 41 Separator Element Replacement 41 Pressure Regulator Adjustment 42 Water Condensate Drain Maintenance 42 Control Line Strainer 42...

Страница 5: ...able to most compressors and the concepts behind these statements are generally applicable to all compressors 1 2 PERSONAL PROTECTIVE EQUIPMENT Prior to installing or operating the compressor owners e...

Страница 6: ...aced immediately to prevent accumulation of liquids or fluid film within the material DO NOT use flammable solvents for cleaning purposes D Disconnect and lock out all power at source prior to attempt...

Страница 7: ...ound to air line anti icer systems G If air line anti icer system antifreeze compound enters the eyes or if fumes irritate the eyes they should be washed with large quantities of clean water for fifte...

Страница 8: ...once it has been lifted clear of the ground F DO NOT attempt to lift in high winds G Keep all personnel out from under and away from the compressor whenever it is suspended H Lift compressor no highe...

Страница 9: ...ther types of compressors the Sullair rotary screw is unique in mechanical reliability with no wear and no inspection required of the working parts within the compressor unit Read MAINTENANCE on page...

Страница 10: ...fan and main motors through the combined aftercooler and fluid cooler thereby removing the compression heat from the compressed air and the cooling fluid and forces it out the top of the machine This...

Страница 11: ...he first filter change and sent to the factory for analysis This is a free service The sample kit with instructions and self addressed container is to be supplied by your Sullair dealer at start up Th...

Страница 12: ...the compressor unit where it lubricates cools and seals the rotors and the compression chamber As the discharge temperature rises above 185 F 85 C due to the heat of compression the thermal valve beg...

Страница 13: ...THIS PAGE INTENTIONALLY LEFT BLANK DESCRIPTION SULL AIR 1100e 1500e 1800e Operator s Manual and Parts List 9...

Страница 14: ...m reduces the fluid carry over to less than 1 ppm parts per million for Sullube or 2 ppm for 24KT A message on the controller indicates if abnormal pressure drop through the separator develops At this...

Страница 15: ...SU_0000084 AIR 1 2 3 1 Compressor 2 Cooler 3 Moisture Separator Figure 2 3 Discharge System DESCRIPTION SULL AIR 1100e 1500e 1800e Operator s Manual and Parts List 11...

Страница 16: ...e pressure regulator controls the inlet control valve The orifice also bleeds any accumulated moisture from the control lines Unload Mode In Excess of 110 PSIG 7 6 BAR When a relatively small amount o...

Страница 17: ...3 Blowdown Valve 4 Pressure Regulator 5 Pressure Relief Valve 6 Receiver Tank 7 Temperature Thermistor 8 Sight Glass Upper Level 9 Sight Glass Lower Level Figure 2 4 Standard Control System DESCRIPTI...

Страница 18: ...6 9 to 7 6 BAR on page 12 The inlet valve also acts as a check valve thus preventing reverse rotation when the compressor is shut down WARNING The Plastic Pipe Institute recommends against the use of...

Страница 19: ...1351 31 5 800 53 2 1351 1098 498 1800 SERIES 1809e 25 53 2 1351 31 5 800 53 2 1351 1122 509 1812e 25 53 2 1351 31 5 800 53 2 1351 1122 509 I Includes standard and 24KT Rated pressure designations appe...

Страница 20: ...ble for operation in higher ambient temperature MOTOR IV STANDARD MODELS Size 15 20 25HP 11 15 18KW Type TEFC Epact Efficiency Three Phase 230 460 Hz 380 415 400 50 Hz Maximum Ambient Temperature 104...

Страница 21: ...Plastic Pipe Institute Recommendation B Adopted January 19 1972 Maintenance of all other components is still recommended as indicated in the Operator s Manual DO NOT MIX DIFFERENT TYPES OF FLUIDS Con...

Страница 22: ...G C B D A 8 000 hours or once a year B 4 000 hours or more frequently if conditions so require C When measured pressure loss exceeds 20 psig 1 3 bar D When measured pressure loss exceeds 10 psig 0 7...

Страница 23: ...THIS PAGE INTENTIONALLY LEFT BLANK SPECIFICATIONS SULL AIR 1100e 1500e 1800e Operator s Manual and Parts List 19...

Страница 24: ...3 5 IDENTIFICATION AIR COOLED UNIT 02250161 035R02 1 1 2 3 6 5 SECTION 3 20 1100e 1500e 1800e Operator s Manual and Parts List SULL AIR...

Страница 25: ...anel 2 Controller 3 E Stop 4 Air Out Connection 5 Air Exhaust 6 Air Inlet 7 Moisture Drain Connection 8 Incoming Customer Power Supply Location Figure 3 2 Identification Air Cooled SPECIFICATIONS SULL...

Страница 26: ...3 6 PIPING AND INSTRUMENTATION AIR COOLED 02250157 525r02 Figure 3 3 Piping and Instrumentation Air Cooled SECTION 3 22 1100e 1500e 1800e Operator s Manual and Parts List SULL AIR...

Страница 27: ...0049 634 1 16 strainer v type 1 4 241771 2 17 valve sol 3wno 1 4 235 n4 02250125 657 2 18 valve pressure regulator 250017 280 1 19 valve shuttle 1 4 dbl chk 408893 1 20 valve sol 2wnc 1 4 200 n4 02250...

Страница 28: ...3 7 WIRING DIAGRAMS Wiring Diagram MFV 02250156_577R04 1 SECTION 3 24 1100e 1500e 1800e Operator s Manual and Parts List SULL AIR...

Страница 29: ...02250156_577R04 2 Figure 3 4 Wiring Diagram MFV SPECIFICATIONS SULL AIR 1100e 1500e 1800e Operator s Manual and Parts List 25...

Страница 30: ...Wiring Diagram VSD 400V 50Hz 460V 60Hz 02250156_119r04 2 SECTION 3 26 1100e 1500e 1800e Operator s Manual and Parts List SULL AIR...

Страница 31: ...02250156_119r04 2 Figure 3 5 Wiring Diagram VSD 400V 50Hz 460V 60Hz SPECIFICATIONS SULL AIR 1100e 1500e 1800e Operator s Manual and Parts List 27...

Страница 32: ...Wiring Diagram VSD 575V 60Hz 02250164_731r01 1 SECTION 3 28 1100e 1500e 1800e Operator s Manual and Parts List SULL AIR...

Страница 33: ...02250164_731r01 2 Figure 3 6 Wiring Diagram VSD 575V 60Hz SPECIFICATIONS SULL AIR 1100e 1500e 1800e Operator s Manual and Parts List 29...

Страница 34: ...SECTION 3 THIS PAGE INTENTIONALLY LEFT BLANK 30 1100e 1500e 1800e Operator s Manual and Parts List SULL AIR...

Страница 35: ...ve surfaces will increase ambient noise levels NOTE Ambient temperatures above 104 F 40 C require that the high ambient option is specified for the compressor 4 2 VENTILATION AND COOLING Air Cooled Co...

Страница 36: ...ation of a line filter s and the installation of isolation valve or valves These considerations are important to ensure a safe and effective system NOTE Discharged air contains a very small amount of...

Страница 37: ...must provide electrical supply power disconnect within sight of machine The fuse protecting the circuit and the compressor must be selected in accordance with the data provided in the general informat...

Страница 38: ...rotation is noted disconnect the power to the starter and exchange any two of the three power input leads then re check rotation A Direction of Rotation decal is located on the motor drive housing to...

Страница 39: ...ure 5 1 WS Controller 5 2 CONTROLLER KEYPAD The WS Controller keypad has two main pads for compressor control To start the compressor operation press the green Start pad To stop compressor operation p...

Страница 40: ...ontinue beyond the status information the display will show a list of control settings The upper line will indicate Show Setting and the name of the setting The lower line shows the present value SA_0...

Страница 41: ...his LED will blink to indicate that the motor may restart The yellow Maintenance indicator comes on whenever there is recommended maintenance or a warning The text display will periodically indicate t...

Страница 42: ...SECTION 5 THIS PAGE INTENTIONALLY LEFT BLANK 38 1100e 1500e 1800e Operator s Manual and Parts List SULL AIR...

Страница 43: ...ble cause and remedy WARNING HIGH PRESSURE HAZARD DO NOT remove caps plugs and or other components when compressor is running or pressurized Stop compressor and relieve all internal pressure before do...

Страница 44: ...Filter Assembly 6 6 AIR FILTER MAINTENANCE Refer to Figure 6 2 Air filter maintenance should be performed when the maintenance gauge shows red with the compressor running full load or once a year whi...

Страница 45: ...length 6mm diameter pin into the radial drilled hole in the separator cap Loosen and rotate counterclockwise to remove the cap 2 Pull out the old element by gripping the end of the element with channe...

Страница 46: ...y 12 months it is necessary to clean the strainer Remove the hex cap from the strainer and remove the strainer screen Clean the screen and reinstall If the screen is damaged the strainer assembly must...

Страница 47: ...erating Pressure Separator requires maintenance Check maintenance indicator under full load conditions High pressure setting in WS Controller set wrong reset Defective valve regulator valve should cau...

Страница 48: ...in Control System Causing Loss of Pressure Signals Check for leaks Inlet Valve Stuck Open Remove the intake hose and check for inlet valve operation Defective Unload Solenoid Valve Check that the val...

Страница 49: ...or the flow and dryness level required Note Filters may also be required to remove particulates liquid oil aerosols or for oil vapor removal Change cartridges as recommended by the filter manufacturer...

Страница 50: ...SECTION 6 THIS PAGE INTENTIONALLY LEFT BLANK 46 1100e 1500e 1800e Operator s Manual and Parts List SULL AIR...

Страница 51: ...of the compressor This can be obtained from the Bill of Lading for the compressor or from the Serial Number Plate located on the compressor Refer to Figure 7 1 02250155_844_Sec7 1 Figure 7 1 SULL AIR...

Страница 52: ...he Representative from whom the compressor was purchased If for any reason parts cannot be obtained in this manner contact the factory directly at the addresses phone and fax numbers listed below SECT...

Страница 53: ...157 500 1 9 kit coil replacement for control solenoid valve 02250155 714 02250157 502 1 10 kit repair for condensate drain solenoid valve 02250155 715 02250157 501 1 11 kit coil replacement for conden...

Страница 54: ...7 3 COMPRESSOR FRAME AND DRIVE A1 02250157 804R04 SECTION 7 50 1100e 1500e 1800e Operator s Manual and Parts List SULL AIR...

Страница 55: ...15 gasket isol to frame p8 02250157 598 3 16 mtr 11 18kw 256tz frame 02250157 658 1 17 tube separator oil return 02250157 679 1 18 frame lift off p8 02250160 379 1 19 elbow 90deg m swvl 1 8 t x 1 8 02...

Страница 56: ...7 3 COMPRESSOR FRAME AND DRIVE CONTINUED A1 02250157 804R04 SECTION 7 52 1100e 1500e 1800e Operator s Manual and Parts List SULL AIR...

Страница 57: ...lug metric thd orng holhx m18 882018 015 1 49 nut hex metric m12 x 1 75 882112 175 5 50 screw hex serr washer m8 x 25 882608 025 6 A1 Tray Drain I Sullair offers an exchange program whereby a remanufa...

Страница 58: ...7 4 AIR INLET SYSTEM 02250157_200r02 SECTION 7 54 1100e 1500e 1800e Operator s Manual and Parts List SULL AIR...

Страница 59: ...mp hose 3 040343 4 6 clamp hose 2 3 8 I D 408300 010 2 7 screw self drill 1 4 x 1 2 834504 050 2 8 washer iso 7093 6 140hv 865706 180 2 9 nut serr flng m8 x 1 25 882508 125 2 10 screw hex serr washer...

Страница 60: ...7 5 DISCHARGE AIR PIPING A1 A2 A3 A4 02250154_771R04 SECTION 7 56 1100e 1500e 1800e Operator s Manual and Parts List SULL AIR...

Страница 61: ...1 2 866316 035 1 8 bushing red hex pltd 1 x 3 4 868904 030 1 9 bushing red hex pltd 1 1 2 x 1 868906 040 1 10 nut serr flng m8 x 1 25 882508 125 2 11 screw hex serr washer m8 x 16 882608 016 2 12 elb...

Страница 62: ...7 6 FLUID PIPING 02250154 767R003 SECTION 7 58 1100e 1500e 1800e Operator s Manual and Parts List SULL AIR...

Страница 63: ...2 219 1 7 screw socket iso 4762 m10 x 80mm 829310 080 2 8 elbow met st thd orfs m27 x 3 4 883627 012 2 9 union str thd iso 6149 m27 x 2 883727 012 1 10 valve thermal 195f 1 1 2 18 VARIOUS 1 A1 To flui...

Страница 64: ...7 7 COOLING AND LUBRICATION SYSTEM A1 A2 A3 02250160 533R004 A4 SECTION 7 60 1100e 1500e 1800e Operator s Manual and Parts List SULL AIR...

Страница 65: ...13 grip cord for so 12 4 st 3 4 250018 497 2 14 wire neoprene 12 4 so ft 850604 012 8 15 washer metric iso7089 8 865408 170 4 16 washer iso 7093 8 140hv 865708 240 3 17 nut serr flng m8 x 1 25 882508...

Страница 66: ...7 8 COMPRESSOR HOUSING RECEIVER TANK AND PARTS 02250157_805r00 SECTION 7 62 1100e 1500e 1800e Operator s Manual and Parts List SULL AIR...

Страница 67: ...ll E8E 02250149 395 1 9 transducer pressure 0 250 ratiometric 02250155 174 1 10 probe rtd 100 ohm plat 3 5 x 6ft 02250155 175 1 11 fitting compress adj 250028 635 1 12 O ring viton 1 7 16 x 3 32 82650...

Страница 68: ...7 9 MOISTURE DRAIN 02250157_143R00 SECTION 7 64 1100e 1500e 1800e Operator s Manual and Parts List SULL AIR...

Страница 69: ...200 050 2 9 elbow entrance 1 2 847715 050 1 10 wire mtw amw 16ga dk blu 850216 016 14 11 connector wire orange 851000 073 2 12 elbow pipe 90m 1 4 x 1 4 860504 025 1 13 nipple pipe hx pltd 1 4 x 1 4 86...

Страница 70: ...7 10 PNEUMATIC CONTROL SYSTEM 02250154_867r02 SECTION 7 66 1100e 1500e 1800e Operator s Manual and Parts List SULL AIR...

Страница 71: ...chk 408893 1 19 bulkhead pipe 1 4 npt 841500 004 1 20 nipple chase cond 1 2 847815 050 2 21 tee male pipe brass 1 4 869825 025 1 22 tee female pipe brass 1 4 878225 025 2 23 elbow pipe 90m 1 4 x 1 4 b...

Страница 72: ...7 11 CONTROL SYSTEM AND ELECTRIC PARTS A1 A2 A4 A6 A7 A5 A3 02250156_917r02 SECTION 7 68 1100e 1500e 1800e Operator s Manual and Parts List SULL AIR...

Страница 73: ...x 6ft 02250155 175 I 1 17 specification encl 2200 19 x 24 5 x 7 02250156 385 1 18 wire 10 gauge ground bond 12 m8 02250157 450 1 19 receptacle s4 program port nema 6p 02250159 547 1 20 cap s4 program...

Страница 74: ...7 11 CONTROL SYSTEM AND ELECTRIC PARTS CONTINUED A1 A2 A4 A6 A7 A5 A3 02250156_917r02 SECTION 7 70 1100e 1500e 1800e Operator s Manual and Parts List SULL AIR...

Страница 75: ...rtd probe No 02250155 175 order replacement probe P N 02250155 175 II This part may vary per machine specification Consult the Sullair factory for details III Plug unused holes in starter with hole pl...

Страница 76: ...7 12 CONTROL SYSTEM AND ELECTRIC PARTS WYE DELTA A1 A7 A3 A4 A2 A6 02250165_275r00 SECTION 7 72 1100e 1500e 1800e Operator s Manual and Parts List SULL AIR...

Страница 77: ...5 x6ft 02250155 175 1 18 link mech intrik ch it frm b e 02250155 676 1 19 specification encl 2200 19 x 24 5 x 7 02250156 385 1 20 wire 10 gauge ground bond 12 m8 02250157 450 1 21 receptacle s4 progr...

Страница 78: ...7 12 CONTROL SYSTEM AND ELECTRIC PARTS WYE DELTA CONTINUED A1 A7 A3 A4 A2 A6 02250165_275r00 SECTION 7 74 1100e 1500e 1800e Operator s Manual and Parts List SULL AIR...

Страница 79: ...shown 1 A6 P C Port 1 I This part may vary per machine specification Consult the Sullair factory for details III Plug unused holes in starter with hole plug part number 409918 002 IV 250014 827 Item 2...

Страница 80: ...7 13 CONTROL SYSTEM AND ELECTRIC PARTS VSD A1 A3 A4 A2 A6 A5 A7 02250165_276r00 SECTION 7 76 1100e 1500e 1800e Operator s Manual and Parts List SULL AIR...

Страница 81: ...175 1 16 specification encl 2200v 19 x 24 5 x 7 02250155 766 1 17 wire 10 gauge ground bond 12 m8 02250157 450 1 18 receptacle s4 program port nema 6p 02250159 547 1 19 cap s4 program port nema 6p 022...

Страница 82: ...7 13 CONTROL SYSTEM AND ELECTRIC PARTS VSD CONTINUED A1 A3 A4 A2 A6 A5 A7 02250165_276r00 SECTION 7 78 1100e 1500e 1800e Operator s Manual and Parts List SULL AIR...

Страница 83: ...ere Shown 1 A7 P C Port 1 I This part may vary per machine specification Consult the Sullair factory for details III Plug unused holes in starter with hole plug part number 409918 002 IV 250014 827 It...

Страница 84: ...7 14 ENCLOSURE 02250155_649R05 SECTION 7 80 1100e 1500e 1800e Operator s Manual and Parts List SULL AIR...

Страница 85: ...starter end p8 p10 02250155 824 1 10 rail roof starter end p8 p10 02250155 825 1 11 pocket drawing holder 3700 02250158 039 1 12 rail vertical starter side p8 p10 02250160 372 1 13 rail vertical p8 p1...

Страница 86: ...7 15 DECAL LOCATION 02250157 768R004 A1 A2 A3 A7 A10 A7 A7 A9 A8 A8 A6 A6 A5 A9 A11 A9 A12 A7 A7 A11 A4 SECTION 7 82 1100e 1500e 1800e Operator s Manual and Parts List SULL AIR...

Страница 87: ...vsd black p8 p10 p12 02250162 215 2 14 decal warning n12 elec encl protc 02250164 823 1 15 decal warning auto start 41065 1 16 decal danger hi voltage 42218 1 17 sign warning comp oil fil cap 49685 1...

Страница 88: ...7 15 DECAL LOCATION CONTINUED 02250157 768R004 A1 A2 A3 A7 A10 A7 A7 A9 A8 A8 A6 A6 A5 A9 A11 A9 A12 A7 A7 A11 A4 SECTION 7 84 1100e 1500e 1800e Operator s Manual and Parts List SULL AIR...

Страница 89: ...A3 Detail view of thermal valve block A4 Face of motor conduit box A5 Attach to inside of starter door A6 Attach to the bottom on inside of starter box A7 Both sides of machine A8 Attach to sub panel...

Страница 90: ...ng proper safety equipment See OSHA standards on safety equipment 250027 932 DANGER Lethal shock hazard inside Disconnect all power at source before opening or servicing 049850 250019_032R01 16 5 20 0...

Страница 91: ...air 250027 935 1 18 decal danger electrocution 49850 1 6 decal parallel wye motor conn 02250146 385 2 16 decal danger hi voltage 42218 1 5 decal en warning mixing fluids 02250110 891 1 20 sign warning...

Страница 92: ...ur Company s Prescribed Safety Practices for Electrical Equipment 250017 903 WARNING WARNING 049852 22 27 15 Do not permit air from this equip ment to contact food stuff except in fullcompi ance with...

Страница 93: ...l cap 49685 1 23 decal warning autostart 250017 903 1 19 decal warning elec shock ground fault 49852 1 22 decal warning food grade lub 250003 144 1 27 sign warning hot surfaces 407408 1 15 decal warni...

Страница 94: ...2 3 7 02250075 045 02250075 540 02250155 495 8 9 02250157_703R00 02250157_732R01 10 11 02250157_749 02250158_358R00 12 02250161 967R02 13 02250162_215R01 SECTION 7 90 1100e 1500e 1800e Operator s Manu...

Страница 95: ...lair com 02250155 495 2 8 decal sullair side graphics 02250157 703 2 9 decal sullair side graphic 02250157 732 1 10 decal maint kit eng 02250157 749 1 11 decal remove before start up 02250158 358 2 12...

Страница 96: ...4 21 24 02250164_823r00 LIFT HERE 241814 250021 564 25 WATER DRAIN 250022 810 28 28 28 02250069 389 LLL 4 32 022500 6 9 394 02250069 394 24 KT 02250069 395 SECTION 7 92 1100e 1500e 1800e Operator s Ma...

Страница 97: ...2250164 823 1 21 decal fork lifting 241814 2 24 decal rotation 3 5 lg 250021 564 1 25 decal water drain 3 3 4 x 1 250022 810 1 28 fluids fluid decal 02250069 389 I 1 fluids fluid decal 02250069 394 I...

Страница 98: ...2 230V 230V 3 3 60 60 Hz H 02250069 397 02250069 397 460V 3 60 Hz 02250069 399 02250069 399 575V 3 60 Hz 02250069 400 02250069 400 32 32 380 415V 3 50 Hz 02250069 403 02250069 403 200V 3 60 Hz 0225006...

Страница 99: ...02250157 736 I 1 32 voltage decal 02250069 397 I 1 voltage decal 02250069 399 I 1 voltage decal 02250069 400 I 1 voltage decal 02250069 403 I 1 voltage decal 02250069 406 I 1 I This decal will vary w...

Страница 100: ...SECTION 7 THIS PAGE INTENTIONALLY LEFT BLANK 96 1100e 1500e 1800e Operator s Manual and Parts List SULL AIR...

Страница 101: ...THIS PAGE INTENTIONALLY LEFT BLANK...

Страница 102: ...nly or 1 219 879 5451 Fax 219 874 1273 CUSTOMER CARE for PARTS and SERVICE 1 888 SULLAIR 7855247 219 874 1835 SULLAIR ASIA LTD Sullair Road No 1 Chiwan Shekou Shenzhen Guangdong PRV PRC POST CODE 5180...

Отзывы: