STULZ CyberRow Chilled Water Series Installation, Operation & Maintenance Manual
(
Dec.
, 2013)
4-29
Factory Default Bitmask Total
129
Factory Default Bitmask Total
3
Factory Default Bitmask Total
0
NOTE:
The default values (
shown in bold italics
) are factory set to generate a custom alarm output on any of the major
alarms and any sensor failure. Only the enabled sensors can generate an alarm. To enable an additional custom alarm, add
the alarm bitmask number to the factory default total and enter the new total for the applicable alarm numbers in the
Custom Alarm Setup screen. If an alarm condition appearing in the following tables is detected, it needs to be reset at
the interface display panel or via the BMS.
Alarms 17 to 24
No.
Description
Bit
mask
De-
fault
17
Humidifi er alarm
1
1
18
High temperature alarm
2
0
19
Low temperature alarm
4
0
20
High humidity alarm
8
0
21
Low humidity alarm
16
0
22
High water temperature CW1
32
0
23
Low water temperature CW1
64
0
24
Loss of power
128
128
Alarms 25 to 32- (
Sensor Failure Alarms)
No.
Description
Bit
mask
Default
25
Lower temperature sensor fail
1
1
26
Middle temperature sensor fail
2
2
27
Optional temperature sensor fail
4
4
28
Upper temperature sensor fail
8
8
29
Return humidity sensor fail
16
16
30
DX1 discharge pressure fail
32
32
31
Static air pressure sensor fail
64
64
32
DX1 suction press sensor fail
128
128
Alarms 33 to 40- (
Sensor Failure Alarms)
No.
Description
Bit
mask
Default
33
DX1 suction temp sensor fail
1
1
34
Custom sensor 1 fail
2
2
35
Reserved
4
0
36
Reserved
8
0
37
Reserved
16
0
38
Reserved
32
0
39
Reserved
64
0
40
Reserved
128
0
Alarms 41 to 48
No.
Description
Bit
mask
Default
41
System Off
1
0
42
BMS keep alive off
2
0
43
Customer alarm 2
4
0
44
Customer alarm 3
8
0
45
Flow switch
16
0
46
Reserved
32
0
47
Reserved
64
0
48
Reserved
128
0
Factory Default Bitmask Total
255
Alarms 1 to 8
No.
Description
Bit
mask
Default
1
Upper Fan alarm
1
1
2
Lower fan alarm
2
2
3
Middle fan alarm
4
4
4
Moisture alarm
8
8
5
Emergency shutdown
16
16
6
Remote shutdown
32
32
7
Customer alarm 1
64
0
8
Airfl ow alarm
128
128
Alarms 9 to 16
No.
Description
Bit
mask
Default
9
Filter alarm
1
0
10
Fire/Smoke alarm
2
2
11
Water detection alarm
4
4
12
Condensate pan alarm
8
8
13
Circuit1 low pressure alarm
16
16
14
Circuit1 high pressure alarm
32
32
15
Dual power input A alarm
64
0
16
Dual power input B alarm
128
0
Factory Default Bitmask Total
191
Factory Default Bitmask Total
62
Service
Menu