4.3.2 Alarms
As programmed into the system controller, an alarm
condition activates the summary alarm logic which
illuminates the alarm key and energizes an audible
alarm. Some alarms are programmed by the factory to
automatically shut down the A/C unit until the alarm
condition is remedied and the alarm is cleared by pressing
the alarm key. Some of the alarms that may be enabled by
the factory are listed in Section 4.5.3.
4.3.2.1 Summary
Alarm
A summary alarm will activate when the controller senses
any programmed alarm condition. This illuminates the
alarm key and if the option is selected, a N.O./N.C.
summary alarm contact may be energized for remote
monitoring of alarm conditions. If certain critical summary
alarm conditions are detected, they will cause the A/C unit
to shutdown.
4.3.2.2 Customer
Alarms
A customer provided digital (on/off switching) alarm sen-
sor may be connected to terminals provided in the electric
box. This alarm input may be for any site specifi c alarm
condition the user wishes to monitor that may or may not
be provided in the standard controller alarms menu; i.e.
Gas Detection, Intrusion Alarm, etc. Upon detection of a
customer alarm, the controller will activate the summary
alarm contact and display a screen message indicating a
customer alarm message. The screen message "
Customer
Alarm 1
" (default) will appear in the controller display
or the user may reconfi gure the controller to display any
alpha-numeric message desired, up to 20 characters long,
in the Service>Options>Custom menu loop (see Section
4.5.5.6.6).
4-9
4.3.2.3 Custom
Alarms
A custom (user confi gured) alarm is activated upon
detection of one or more programmed alarm conditions
as set by the operator in the Service>Options>Custom
menu loop (see Section 4.5.5.6.7). When a custom alarm
condition is detected, a summary alarm is signaled and a
designated set of N.O. & N.C. Custom Alarm relay contacts
may be energized to provide remote indication of the
specifi c alarm condition(s).
For example you may want to be notifi ed when a change
fi lter alarm is annunciated, giving notice that the air
fi lters need to be cleaned or replaced. That way you are
alerted before the fi lters are so badly clogged that airfl ow
is reduced to a point where a "Loss of airfl ow" alarm is
activated.
The controller may be factory confi gured to activate up to
three custom alarms. One custom alarm with relay contacts
is provided as a standard and up to 2 additional custom
alarms may be provided as an option.