E09.012.246 Manual S-WG
80
Menu B: Hot water
B B
D H d s c D i f 2
1 0
° C
Function for the direct hot water boiler.
This parameter is the hysteresis of the selected
HW temperature of the boiler.
Menu B: Hot water
B C
D H d s c l n t 2 3
2 0 0 S e c
Function for the direct hot water boiler.
This parameter is the integration time of the selected
HW temperature of the boiler.
Menu B: Hot water
B D
D H d s c O f f 3
4
° C
Function for the cascaded direct hot water boilers.
This parameter is the offset of the selected
HW temperature of the cascaded boilers.
Menu B: Hot water
B E
D H d s c D i f 3
8
° C
Function for the cascaded direct hot water boilers.
This parameter is the hysteresis of the selected
HW temperature of the cascaded boilers.
Menu B: Hot water
B F
D H i s c D i f 4
5
° C
Function for the indirect hot water supply of the
boiler (tank).
This parameter is the hysteresis of the selected
HW temperature of the calorifier/tank.
Menu B: Hot water
B G
D H i d e t g r a d
3
° C
Function for the indirect hot water supply of the
boiler (tank).
This parameter detects an (an accelerated) hot water
demand, when a larger (water) amount is being used.
Menu C: Cascade
C 1
M a x C a s c U n t
1 1
Function for the cascading of the boiler(s).
This parameter sets the total amount of cascaded boilers.
(Max. 12 boilers).
The screen texts on these pages are
standard part of the software and
apply to CH systems (boilers) and/or
DHW devices (water heaters).
Содержание S-WG 100
Страница 13: ...E09 012 246 Manual S WG 14 3 3 S WG tanks 300 Ltr 450 Ltr ...
Страница 14: ...E09 012 246 Manual S WG 15 750 Ltr ...
Страница 33: ...E09 012 246 Manual S WG 34 7 4 Electrical schematics ...
Страница 34: ...E09 012 246 Manual S WG 35 ...
Страница 39: ...E09 012 246 Manual S WG 40 For large capacity installations more than two water heaters consult STREBEL ...
Страница 122: ...E09 012 246 Manual S WG 123 notes ...
Страница 123: ...E09 012 246 Manual S WG 124 notes ...
Страница 124: ......