E09.012.246 Manual S-WG
28
C: Single pipe for flue gas outlet only
(air supply from plant room).
Example C
The total resistance is less than 200 Pa. This flue gas/air supply system is functional.
100
4
m
2m
3
m
2m
2
m
Water heater type:
S-WG 100
Flue gas
Diameter: 100 mm.
Number
Pa
Pa total
Straight tube m¹
total
13
4
52
Bend
90°
2
4
8
Bend
45°
2
2
4
Flue outlet
H/D = 1.0
1
15.2
15.2
Total resistance flue gas outlet:
79.2