E09.012.246 Manual S-WG
78
Menu A: Heating
A 6
H E
c O f f
3
4
° C
Select the cascaded boilers supply temperature control.
This parameter is the offset of the selected CH
supply temperature of EACH boiler of the total cascade.
Menu A: Heating
A 7
H E
c P r b
3
2 5
° C
Select the cascaded boilers supply temperature control.
This parameter is the proportional range of the selected
CH supply temperature of EACH boiler of the total
cascade and of the external (cascade) sensor.
Menu A: Heating
A 8
H E
c l n t
3
8 0
S e c
Select the cascaded boilers supply temperature control.
This parameter is the integration time of the selected
CH supply temperature of EACH boiler of the total
cascade and of the external (cascade) sensor.
Menu A: Heating
A 9
T i m e r C o n t
0
Function to activate "external time controller":
0 = Off
1 = On
Connect to 13-14. Contact closed = daytime setting,
Contact open = night-time setting.
Menu B: Hot water
B 1
D H i p m p / t w v
1
Hot water function of the boiler by:
0 = pump
1 = 3-way valve
Menu B: Hot water
B 2
D H i f l o w L O
2 5
° C
Hot water function of the boiler. This parameter is the
CH supply temperature LOW level with an indirect
hot water demand.
Menu B: Hot water
B 3
D H i f l o w H I
8 5
° C
Hot water function of the boiler. This parameter is the
CH supply temperature HIGH level with an indirect
hot water demand.
The screen texts on these pages are
standard part of the software and
apply to CH systems (boilers) and/or
DHW devices (water heaters).
Содержание S-WG 100
Страница 13: ...E09 012 246 Manual S WG 14 3 3 S WG tanks 300 Ltr 450 Ltr ...
Страница 14: ...E09 012 246 Manual S WG 15 750 Ltr ...
Страница 33: ...E09 012 246 Manual S WG 34 7 4 Electrical schematics ...
Страница 34: ...E09 012 246 Manual S WG 35 ...
Страница 39: ...E09 012 246 Manual S WG 40 For large capacity installations more than two water heaters consult STREBEL ...
Страница 122: ...E09 012 246 Manual S WG 123 notes ...
Страница 123: ...E09 012 246 Manual S WG 124 notes ...
Страница 124: ......