Table 3–1 HSD05 LED Indicator Codes
Code
Problem
Resolution
11
DSSI port problem
Ensure that DSSI termination power is supplied by either
the host bus or the HSD05 array controller. Check all
DSSI bus connections and terminations.
12
SCSI port problem
Ensure that SCSI termination power is supplied by either
the host bus or the HSD05 array controller. Check all
SCSI bus connections and terminations.
3.4 HSD05 Error Logs
The HSD05 array controller logs error conditions in the OpenVMS error log
file ERRLOG.SYS. To retrieve this information, use the OpenVMS command
ANALYZE/ERROR_LOG. Refer to the applicable OpenVMS documentation to
read this error log when troubleshooting the HSD05 array controller.
The HSD05 array controller reports the following two types of error logs:
•
Type 1
error logs are SCSI port related.
•
Type 2
error logs are SCSI command related.
For each of the types of error logs, there are also separate formats for disk and
tape devices.
The following two tables contain information to be used in interpreting HSD05
array controller errors during OpenVMS error log analysis:
•
Table 3–2
lists the codes in the error logs generated by the HSD05 array
controller.
•
Table 3–3
lists the SCSI bus phases reported by the HSD05 array controller.
Table 3–2 Port Error Codes
Code
(Hexadecimal) Port Status
2000
Internal sync problem.
4002
Internal inconsistency error; tried to send an unsupported SPORT opcode.
4007
Internal inconsistency error; tried to send an unsupported message.
8000
Reserved.
8001
Reserved.
8003
Double Check condition encountered. Check condition status returned on
a Request Sense due to previous check condition status.
8004
Unsupported SCSI status returned by target.
8005
Unsupported message received.
8006
Target rejected a non-rejectable message.
8008
Phase transition timeout.
8009
Gross error bit was set in SCSI chip.
800A
Parity error bit was set in SCSI chip.
(continued on next page)