P 09.04 Event: I-Max
Default: IG (Hidden)
Event Group: HI
Number: 02
Options:
IG
A (Stop feeder)
W1 (Warning – manual reset)
W2 (Warning – Automatic reset)
Normally Hidden
This parameter determines the type of event that is generated when the feedrate exceeds the value
specified in P09.03 Value for I-Max.
This parameter is normally set to IG (Ignore)
P 09.05 Value for Q-Min
Default: 60.0 % Q
Min: -10.0 % Q
Max: 200.0 % Q
This parameter sets the point at which a minimum belt load event is generated.
This parameter is normally set to 60 % of the nominal belt load (calculated from the nominal flow rate
and the nominal belt speed).
P 09.06 Event: Q-Min
Default: IG
Event Group: LO
Number: 03
Options:
IG
A (Stop feeder)
W1 (Warning – manual reset)
W2 (Warning – Automatic reset)
This parameter determines the type of event that is generated when the feedrate is less then the
value specified in P09.05 Value for Q-Min. Set this value to W2 to simulate the 196NT low density
alarm.
This parameter is normally set to IG (Ignore)
P 09.07 Value for Q-Max
Default: 120.0 % Q (Hidden)
Min: -10.0 % Q
Max: 200.0 % Q
Normally Hidden
This parameter sets the point at which a maximum belt load event is generated.
This parameter is normally set to 120 % of the nominal belt load (calculated from the nominal flow
rate and the nominal belt speed).
Содержание DISOCONT Tersus DT-9
Страница 2: ......
Страница 8: ...DISOCONT Tersus DT 9 Configuration and Operations Manual Schenck Process Group 6 ...
Страница 30: ...DISOCONT Tersus DT 9 Configuration and Operations Manual Schenck Process Group 28 ...
Страница 40: ...DISOCONT Tersus DT 9 Configuration and Operations Manual Schenck Process Group 38 ...
Страница 50: ...DISOCONT Tersus DT 9 Configuration and Operations Manual Schenck Process Group 48 ...
Страница 150: ...DISOCONT Tersus DT 9 Configuration and Operations Manual Schenck Process Group 148 ...
Страница 154: ...DISOCONT Tersus DT 9 Configuration and Operations Manual Schenck Process Group 152 ...