DISOCONT® Tersus (DT-9) Configuration and Operations Manual
©Schenck Process Group
138
Event Group: System Message
SY-01
Memory Error
( P 06.14 )
Error has been detected by cyclic check of program and parameter memories. If SY 01 is
output immediately after power-up.
Call the "Load Default Parameters" function. If this does not help, contact Stock service; in
most cases the controller is inoperable.
SY-07
Communication VHM
( P 01.01 )
Normally disabled.
Communications has been lost between the DT-9 controller and the touch screen display
for more then 10 seconds.
Action:
•
Check cable connections.
SY-08
Cyclic Communication Host
( P 22.03 )
Normally disabled and hidden.
Interruption of serial communication exceeds the timeout period.
Action:
•
Check cabling.
SY-12
Communications ARM7
( P 01.02 )
This parameter selects the error condition generated when communications between the
ARM9 main processor and the ARM7 auxiliary processor are lost.
Action:
•
Check cable connections between boards.
•
Replace controller.
Содержание DISOCONT Tersus DT-9
Страница 2: ......
Страница 8: ...DISOCONT Tersus DT 9 Configuration and Operations Manual Schenck Process Group 6 ...
Страница 30: ...DISOCONT Tersus DT 9 Configuration and Operations Manual Schenck Process Group 28 ...
Страница 40: ...DISOCONT Tersus DT 9 Configuration and Operations Manual Schenck Process Group 38 ...
Страница 50: ...DISOCONT Tersus DT 9 Configuration and Operations Manual Schenck Process Group 48 ...
Страница 150: ...DISOCONT Tersus DT 9 Configuration and Operations Manual Schenck Process Group 148 ...
Страница 154: ...DISOCONT Tersus DT 9 Configuration and Operations Manual Schenck Process Group 152 ...