DISOCONT® Tersus (DT-9) Configuration and Operations Manual
©Schenck Process Group
106
P 15.11 Event: Discharge Pluggage
Default: A
Event Group: WM
Number: 07
Options:
IG (Ignore)
A (Stop feeder)
W1 (Warning – manual reset)
W2 (Warning – Automatic reset)
This parameter specifies the event that is generated when a discharge pluggage is detected.
This parameter is normally set to A (Stop feeder). It can be set to IG (Ignore) to disable the discharge
pluggage event.
P 15.12 DI: Coal on Belt Switch
Default: DI 7 - High
Options:
n/a (not used)
DI 1 thru DI 12 – High/Low
This parameter specifies the digital input used for the Coal on belt switch (LSFB),
This parameter is normally set to DI 7 – High (terminal block X3-6) and is connected to wire 108 if a
coal on belt switch is installed on the feeder. It can be set to n/a (not use) to disable the coal on
belt input.
P 15.13 Loss of Flow Delay
Default: 1s
Min: 0 s
Max: 50 s
This parameter specifies the delay between the time that a loss of material on the belt is detected
(coal on belt switch is inactive) and the time that the Loss of material event is generated. It is the
same as Setup 39 (Loss of Flow Delay) on the 196NT.
This parameter is normally set to 1 second.
Note: The loss of flow event can be disabled by setting P15.14 Loss of material to IG (Ignore).
P 15.14 Event: Loss of Material
Default: IG
Event Group: WM
Number: 08
Options:
IG (Ignore)
A (Stop feeder)
W1 (Warning – manual reset)
W2 (Warning – Automatic reset)
This parameter specifies the event that is generated when a loss of material is detected (coal on belt
switch is inactive).
This parameter is normally set to A (Stop feeder). It can be set to IG (Ignore) to disable the Loss of
material event.
Содержание DISOCONT Tersus DT-9
Страница 2: ......
Страница 8: ...DISOCONT Tersus DT 9 Configuration and Operations Manual Schenck Process Group 6 ...
Страница 30: ...DISOCONT Tersus DT 9 Configuration and Operations Manual Schenck Process Group 28 ...
Страница 40: ...DISOCONT Tersus DT 9 Configuration and Operations Manual Schenck Process Group 38 ...
Страница 50: ...DISOCONT Tersus DT 9 Configuration and Operations Manual Schenck Process Group 48 ...
Страница 150: ...DISOCONT Tersus DT 9 Configuration and Operations Manual Schenck Process Group 148 ...
Страница 154: ...DISOCONT Tersus DT 9 Configuration and Operations Manual Schenck Process Group 152 ...