DISOCONT® Tersus (DT-9) Configuration and Operations Manual
©Schenck Process Group
64
9.2.3 Parameter Group 03 - Control Sources
This parameter group is used to select the control sources for use during Remote mode operation.
P 03.01 Feeder Start
Default: DI 2 – High (Hidden)
Options:
NO (not used)
DI 1 thru DI 14 – High/Low
Normally Hidden
This parameter selects the digital input used as the feeder start command.
Caution:
This is a static input! Switching to remote control mode with the start input activated will
start the feeder.
This parameter is normally set to DI 2 – High (terminal block X1-4) and is connected to wire 112.
P 03.02 Feedrate Setpoint
Default: AI 1
Options:
OP (Operator Panel)
FB (Field Bus)
R-L (Raise/Lower Contacts)
AI (Analog input)
This parameter selects the source for the feedrate demand signal and can be set to the
following values:
AI 1 for use with an analog (usually 4-20mA) input signal on SIG+ and SIG-
R-L for use with the Raise/Lower input signals (See P03.07 and P03.08)
OP for use with EasyServe
FB or remote control using a Field Bus
This parameter is normally set to AI 1 and is connected to wires Sig+ and Sig-.
P 03.03 Setpoint Range
Default: 20.00 mA
Min: 0.00 mA
Max: 1000.00 mA
This parameter determines the nominal 100% signal level for the analog input channel. It should be
set to 20.0 for a 0-20mA, 4-20mA or 0-10V input.
This parameter is normally set to 20.00 mA and is only active when P03.02 is set to an analog
input signal.
Note:
When an analog input card is used, the input jumper must be set toward the outside of the card
for a voltage input signal and toward the middle of the card for a current input signal.
Содержание DISOCONT Tersus DT-9
Страница 2: ......
Страница 8: ...DISOCONT Tersus DT 9 Configuration and Operations Manual Schenck Process Group 6 ...
Страница 30: ...DISOCONT Tersus DT 9 Configuration and Operations Manual Schenck Process Group 28 ...
Страница 40: ...DISOCONT Tersus DT 9 Configuration and Operations Manual Schenck Process Group 38 ...
Страница 50: ...DISOCONT Tersus DT 9 Configuration and Operations Manual Schenck Process Group 48 ...
Страница 150: ...DISOCONT Tersus DT 9 Configuration and Operations Manual Schenck Process Group 148 ...
Страница 154: ...DISOCONT Tersus DT 9 Configuration and Operations Manual Schenck Process Group 152 ...