DISOCONT® Tersus (DT-9) Configuration and Operations Manual
©Schenck Process Group
79
P 07.04 DI: Source Belt Sensor
Default: n/a (Hidden)
Options:
n/a (not used)
DI 13 – High/Low
Normally Hidden
This parameter is used to specify the digital input used for the belt slip sensor. The slip sensor is
connected to a driven roller and generates a frequency input proportional to the belt speed. This
value is compared to the tachometer signal from the motor to detect belt slippage at the head pulley.
See also: parameters P 07.08 Event: Belt Slip and P 07.09 DO: Belt Slip.
This parameter is normally set to n/a.
P 07.05 BIC Active
Default: NO (Hidden)
Options:
NO
YES
Normally Hidden
This parameter is used to activate the moisture Belt Influence Compensation (BIC) system. The BIC
system is used in batching feeders to tare individual sections of the belt separately so that batches
that are less then a full belt length are weighted accurately.
The BIC feature is not used in continuous feeding systems and this parameter should always be set
to NO.
P 07.06 DI: BIC freeze
Default: n/a (Hidden)
Options:
n/a (not used)
DI 1 thru DI 14 – High/Low
Normally Hidden
This parameter is used specify a digital input that is used to freeze the tare value while the BIC
feature is active.
This parameter is normally set to n/a.
P 07.07 Slip Value
Default: 10.0 % LB (Hidden)
Min: 0.0 %
Max: 20.0 %
Normally Hidden
This parameter specifies the maximum amount that the belt speed measured by the belt slip input
can differ from belt speed measured by the tachometer input, without generating an error.
This parameter is normally set to 10.0 % LB.
Содержание DISOCONT Tersus DT-9
Страница 2: ......
Страница 8: ...DISOCONT Tersus DT 9 Configuration and Operations Manual Schenck Process Group 6 ...
Страница 30: ...DISOCONT Tersus DT 9 Configuration and Operations Manual Schenck Process Group 28 ...
Страница 40: ...DISOCONT Tersus DT 9 Configuration and Operations Manual Schenck Process Group 38 ...
Страница 50: ...DISOCONT Tersus DT 9 Configuration and Operations Manual Schenck Process Group 48 ...
Страница 150: ...DISOCONT Tersus DT 9 Configuration and Operations Manual Schenck Process Group 148 ...
Страница 154: ...DISOCONT Tersus DT 9 Configuration and Operations Manual Schenck Process Group 152 ...