DISOCONT® Tersus (DT-9) Configuration and Operations Manual
©Schenck Process Group
105
P 15.07 DI: Reset Totalizer 1
Default: n/a (not used – Hidden)
Options:
n/a (not used)
DI 1 thru DI 14 – High/Low
Normally Hidden.
This parameter specifies the digital input used to remotely reset totalizer 1. The totalizer is reset on
the rising edge of the signal.
This function is not used and this parameter should be set to n/a (not used).
P 15.08 DI: Reset Totalizer 2
Default: n/a (not used – Hidden)
Options:
n/a (not used)
DI 1 thru DI 14 – High/Low
Normally Hidden.
This parameter specifies the digital input used to remotely reset totalizer 2. The totalizer is reset on
the rising edge of the signal.
This function is not used and this parameter should be set to n/a (not used).
P 15.09 DI: Discharge Pluggage
Default: DI 5 - High (Hidden)
Options:
n/a (not used)
DI 1 thru DI 14 – High/Low
Normally Hidden.
This parameter specifies the digital input used for the discharge pluggage switch (LSFD). It is
internally programmed as a failsafe input. When the parameter is set to HIGH, open contact (low
signal) on the input will produce an event.
This parameter is normally set to DI 5 – High (terminal block X2-4) and is connected to wire 109.
P 15.10 Discharge Pluggage Delay
Default: 2 s
Min: 0 s
Max: 50 s
This parameter specifies the delay between the time that a discharge pluggage is detected and the
time that the discharge pluggage event is generated. It is the same as Setup 16 (Discharge
Pluggage Delay) on the 196NT.
This parameter is normally set to 2 seconds.
Содержание DISOCONT Tersus DT-9
Страница 2: ......
Страница 8: ...DISOCONT Tersus DT 9 Configuration and Operations Manual Schenck Process Group 6 ...
Страница 30: ...DISOCONT Tersus DT 9 Configuration and Operations Manual Schenck Process Group 28 ...
Страница 40: ...DISOCONT Tersus DT 9 Configuration and Operations Manual Schenck Process Group 38 ...
Страница 50: ...DISOCONT Tersus DT 9 Configuration and Operations Manual Schenck Process Group 48 ...
Страница 150: ...DISOCONT Tersus DT 9 Configuration and Operations Manual Schenck Process Group 148 ...
Страница 154: ...DISOCONT Tersus DT 9 Configuration and Operations Manual Schenck Process Group 152 ...