10.5.18 X300: Brake 24 V supply
X300 is used to supply the brake.
ATTENTION!
Device damage due to overload!
If the 24 V
DC
power supply is looped to multiple devices over the terminal, the terminal may be
damaged by a current that is too high.
▪
Make sure that the current over the terminal does not exceed the value 15 A (UL: 10 A).
Electrical data
Single-axis controller
Double-axis controller
U
1
+24 V
DC
, +25%/−0%
I
1max
2.5 A
2 × 2.5 A
Tab. 134: Electrical data of the control unit brake control
Pin
Designation
Function
1 | 3
2 | 4
1
+
24 V
DC
supply for the brake; bridged in the
terminal; design in accordance with EN
60204: PELV, secondary grounded,
recommended fuse protection: max. 15 AT
15
2
3
−
Reference potential for power supply voltage
of the brake
4
Tab. 135: X300 connection description
For connecting wiring, observe the terminal specifications in the chapter
.
Cable requirements
Feature
All sizes
Max. cable length
30 m
Tab. 136: Cable length [m]
15
For UL-compliance, use of a 10 A fuse (time delay) is required. Be sure that the fuse meets certification
requirements for DC voltage in accordance with UL 248.