CAUTION: The M2B controller automatically defaults to a 250
o
F (121.1
o
C)
set-stop limit, water temperature control unit (TCU) configuration. All
special configurations. i.e. 4-20 MA scaling, will be lost. Please record
menu variables before performing a factory default. If you have an oil TCU,
the controller must be re-configured for a high temperature 550
o
F
(287.7
o
C) set-stop limit.
High Temperature Oil
Re-configuration
• Depress and hold the UP and ENTER keypads simultaneously for five
(5) seconds to enter the secure menu.
• “
” will appear in the left display and “
.
..
.
” will appear in the right
display.
• Depress the INDEX keypad until “
)
))
)
” appears in the left display and
“
” appears in the right display.
• Depress the UP arrow until “
” appears in the right display.
• Depress the DOWN and ENTER keypads simultaneously to enter the
parameter.
• Both the displays will flash “
&&
&&
&&
&&
” then “
“ indicating the re-boot is
complete.
• Depress the SET POINT keypad for short cut to the run mode, or, wait
thirty (30) seconds for auto exit to run mode.
∆