Program selection Name
Option Meaning
07
Equalizing charge
function
EQE
Activating equalizing charge
function
EQD
Deactivating equalizing charge
function
08
Voltage for
equalizing charge
If "USE" has been selected in program 01,
this program can be used
15.0 V
12 V rated voltage:
Can be set from 12.0 V to 16.0 V
(default setting: 14.1 V)
30.0 V
24 V rated voltage:
Can be set from 24.0 V to 32.0 V
(default setting: 28.2 V)
60.0 V
48 V rated voltage:
Can be set from 48.0 V to 64.0 V
(default setting: 56.4 V)
If "LIO" has been selected in program 01,
this program can be used
30.0 V
30 A version:
Can be set from 9.0 V to 32.0 V
60.0 V
50 A version:
Can be set from 9.0 V to 64.0 V
09
Charging current
for equalizing
charge
50 A
Only for the 50 A version:
Maximum charging current 50 A,
can be set from 5 A to 50 A in
increments of 5 A
30 A
Only for the 30 A version:
Maximum charging current 30 A,
can be set from 5 A to 30 A in
increments of 5 A
10
Duration of the
equalizing charge
240
Can be set from 5 min to 900 min
in increments of 5 min
(default setting: 240 min)