Program selection Name
Option Meaning
04
Voltage of the
absorption
charge
If "USE" has been selected in program 01,
this program can be used
14.4 V
12 V rated voltage:
Can be set from 12.0 V to 16.0 V
(default setting: 14.4 V)
28.8 V
24 V rated voltage:
Can be set from 24.0 V to 32.0 V
(default setting: 28.8 V)
57.6 V
48 V rated voltage:
Can be set from 48.0 V to 64.0 V
(default setting: 57.6 V)
If "LIO" has been selected in program 01,
this program can be used
28.8 V
30 A version:
Can be set from 9.0 V to 32.0 V
57.6 V
50 A version:
Can be set from 9.0 V to 64.0 V
05
Duration of the
absorption
charge
120
Can be set from 10 min to
900 min in increments of 5 min
(default setting: 120 min)
06
Voltage for float
charge
If "USE" has been selected in program 01,
this program can be used
14.1 V
12 V rated voltage:
Can be set from 12.0 V to 16.0 V
(default setting: 14.1 V)
28.2 V
24 V rated voltage:
Can be set from 24.0 V to 32.0 V
(default setting: 28.2 V)
56.4 V
48 V rated voltage:
Can be set from 48.0 V to 64.0 V
(default setting: 56.4 V)
If "LIO" has been selected in program 01,
this program can be used
28.2 V
30 A version:
Can be set from 9.0 V to 32.0 V
56.4 V
50 A version:
Can be set from 9.0 V to 32.0 V