System-Manager  TAROM | 716148 

page 15 

V09_45A 

storage temperature 

-25°C...80°C 

Connecting screws 

16/25mm² 

Weight 

400g 

Dimensions 188x128x49mm 
Type of protection 

IP22 

8.2  Controlling Data at 25°C 

 

2401 

4401 

programmable 

13,0V...14,5V 26;0V...29,0V 

52,0V...58,0V 

end of charge (float) voltage  

Factory adjustment 

13,7V 27,4V 

54,8V 

programmable 

13,5V...15,0V 

27;0V...30,0V 

54,0V...60,0V 

Factory adjustment 

14,4V 

28,8V 

57,6V 

Quick charging 
boost charging 

activation 

< 12,7V 

<25,4V 

< 50,8V 

programmable 

14,0V...15,0V 27;0V...30,0V 

56,0V...62,0V 

Factory adjustment 

14,7V 29,4V 

58,8V 

equal charging 

activation 

< 12,4V 

<24,8V 

< 49,6V 

programmable 

11,0V...12,5V 

Deepcharging  protection 

Factory adjustment 

11,4V 

programmable 

11,8V...13,3V 

Load reconnection 

Factory adjustment 

12,6V 

Charging process 

IU-characteristic  with PWM at 20Hz 

low voltage

 

< 10,5V 

<21,0V 

< 44,0V 

high voltage 

increasing the programmed value by 0,3V 

high temperature 

75°C inside, reset occurs automatically at 50°C 

Voltage tolerance 

+/- 50mV 

+/- 100mV 

+/-200mV 

Current tolerance 
<40% nominal current 
Nominal current 

 

5% 

10% 

 

5% 

10% 

 

5% 

10% 

9  Malfunctions And Errors 

The System-Manager is designed for many years of constant use. Nevertheless, there may be faults. It is very often, 
however, that the causes for these faults and errors do not occur in the System-Manager itself, but in the peripheral 
system components. The following description should be used as a helpful guide to find the sources of malfunctions and 
to put the device into operation as soon as possible so that unnecessary costs can be avoided. Certainly not all errors 
are listed below. You will find the most common errors and symptoms covering the major part of all possible errors. Send 
in the System-Manager only when you are sure that none of the below-described errors has occurred. 

The System-Manager is protected against damage by various measures. Nevertheless, always take utmost care in the 
proper operation of the System-Manager. Short hints of the malfunctions are indicated with the help of the LCD display. 
However, errors are only properly indicated in which the system has been properly installed. If there are other 
malfunctions than the ones described below, please check first of all if the System-Manager has been connected to the 
battery, the module and the loads correctly in the right polarity. Afterwards, check the safety fuses. In each case of 
malfunction, the System-Manager automatically switches off the load. 

Error 
message / 
Symptoms 

Meaning 

Remedy 

Defective 
fuses 

Usually caused by wrong polarity at the battery connections 

 

Check the proper polarity of the 
connections and after having fixed the 
error, install the spare fuses 

The indication 
on the LCD 
display went 
out 

 

There is no current or voltage feed from the battery, the 
reason could be a defective fuse 

 

current operating temperature is too high or too low 
above/below the operating  temperature, causing LCD 
not to function 

 

Check the battery connections and 
fuses 

 

Check the working temperature 

 

Reinstall the System-Manager 
disconnect everything and connect it 
again in the right order 

“module 

The PV module current exceeds the max. currents allowed. 

 

The solar PV array exceeds the 

Содержание Solarix 2401

Страница 1: ...on by internal fuse Automatic electronic fuse Short circuit protection of load and module Overvoltage protection at module input Open circuit protection without battery Reverse current protection at n...

Страница 2: ...User and Operation manual Specially designed for hybrid systems and telecommunications Steca Solarix 2401 4401 716 148 Z02 09_45 PHOTOVOLTAIK PHOTOVOLTAIC PHOTOVOLTAIQUE FOTOVOLTAICA EN...

Страница 3: ...3 Sub Menu 8 6 Installation 10 6 1 Precautions 10 6 2 Location Of Installation 10 6 2 1 Installation On Walls 11 6 2 2 Rules for mounting the System Manager 11 6 3 Preparations 11 6 3 1 Assemblies 11...

Страница 4: ...g on the PV system Before you start work Read the chapter Installation chapter 6 page 10 Make sure that all Precautions chapter 6 1 page 10 are taken Only start to install your System Manager when you...

Страница 5: ...by manufacturer are connected to this System Manager the user has to accept the consequences CAUTION Opening the System Manager connecting cover excluded as well as use other than prescribed by the m...

Страница 6: ...stem is set for use with lead accumulators batteries with liquid electrolyte and can be set for accumulators with fixed electrolyte like gel batteries The System Manager can be used for all types of s...

Страница 7: ...e corresponding final voltages If the Boost Charge voltage level is too high in comparison with the module voltage reduced by wire losses the countdown may never be started and your battery is therefo...

Страница 8: ...through the controller I_mod is the charging current produced by the solar modules When the voltage of the battery is getting near the final charge voltage the module current I_mod is substantially hi...

Страница 9: ...s can be changed by this scrolling action By pressing OK the displayed menu window is activated and the value is indicated Pressing OK once again leads to a closure of the window without adjustment Af...

Страница 10: ...V 30 0V 54 0V 60 0V The equalisation charging can be programmed similar to adjusting the boost charging Press OK to enter edit the equalisation charge voltage by pressing the arrow keys and confirm se...

Страница 11: ...PV system s efficiency and performance The solar PV array should be installed in a way that in the most unfavourable case the voltage drop is not so high that the battery can not be charged completel...

Страница 12: ...Make sure that the heat sink is well ventilated when mounting 6 3 Preparations 6 3 1 Assemblies Before installation lay out all cables junction boxes and safety fuses cut into sections isolate on both...

Страница 13: ...s to the System Manager s battery connection terminals the symbol shows a rectangular battery with and indicators and tighten securely with a proper slot screwdriver Pay attention to the right polarit...

Страница 14: ...In addition to the electronic fuse device mentioned above the System Manager has also been protected by regular fuses which have been rated far beyond nominal currents to prevent false blowing of the...

Страница 15: ...round for all system components All plus connections are internally connected anyway in the System Manager 6 7 2 Negative Grounding If Negative Grounding is used only one minus connection from any one...

Страница 16: ...ssible so that unnecessary costs can be avoided Certainly not all errors are listed below You will find the most common errors and symptoms covering the major part of all possible errors Send in the S...

Страница 17: ...ischarged deeply or increase solar array to add energy to the system Connect all loads through the System Manager to avoid strong discharge of the battery No module is connected otherwise module modul...

Страница 18: ...aired nor replaced or if this does not occur within a suitable period in spite of the specification of an extension period in writing by the customer the reduction in value caused by the fault shall b...

Страница 19: ......

Страница 20: ......

Страница 21: ...716148...

Отзывы: