background image

However, there are some double errors that may lead to the destruction of the System-Manager or components 
(consumer components, modules ), such as: 

  reverse polarity battery connection on the solar PV terminals 

  One battery wire on the module terminal, the other on the load terminal. 

  A wrong voltage source (grid current with 230VAC ) on the solar PV terminals 

6.7  Grounding 

By grounding the negative poles of the loads, battery and modules together, the electronic components that are 
necessary for the regulation and the safety fuse are bypassed. In this way, internal protection components are also 
deactivated and the System-Manager can be destroyed, as well as damage to the PV system may occur. 

6.7.1  Positive Grounding 

The following passages describe some of the technical 

possibilities of 

a po grounding scheme.  The aim is to always 

maintain the 

System-Manager's proper functions and still achieve 

grounding to 

all the main components. National regulations of the 

operational 

area must be adhered to by the installing electrician. Loss of 

the “safety 

low voltage status” arising from grounding has to be 

compensated 

by corresponding insulation methods of active parts 

(protection 

against direct contact). 

A+

A-

L-

L+

M+

M-

When grounding at the plus-side is done, it can also be considered as common ground for all system components. All 
plus connections are internally connected anyway in the System-Manager. 

6.7.2  Negative Grounding 

If Negative Grounding is used, only one minus connection 

from any 

one the components, i.e. module, battery or load can be 

grounded. 

When your solar system requires a minus ground (e. g. 

battery 

minus), only this component can be connected to ground. A 

connection 

with further minus poles (module or load) bypasses the 

control 

elements and the fuse. This can lead to a malfunction and 

destruction 

of the System-Manager.  

A+

A-

L-

L+

M+

M-

In systems with required load-minus-grounding (e.g. 

grounding 

of aerials), all further components have to be connected with the grounds floating. 

7  Maintenance 

The System-Manager depends on its heat sink’s cooling area to meet its technical specifications. Therefore, the heat sink 
must be kept clean of dust and debris that hampers cooling efficiency. 

As far as the fuse and the cables are concerned, they must be checked for corrosion periodically. Due to corrosion, the 
transfer resistance increases and the contacts could become so hot that damage occurs. 

8  Technical Data 

8.1  Performance Data 

Reglertyp 

2401 

4401 

System voltage 

12V 

24V 

48V 

Max. input voltage 

48V 

90V 

Nominal load current at 20°C 

40A 

40A 

Nominal discharge current at 20°C 

10A 

10A 

max. current for 10s 

55A 

55A 

Surge current for 0,5s 

60A 

60A 

max. pulse current (200ms) 

180A 

180A 

Own consumption 

14 mA 

Temp. range during operation 

-25°C...50°C 

System-Manager  TAROM | 716148 

page 14 

V09_45A 

Содержание Solarix 2401

Страница 1: ...on by internal fuse Automatic electronic fuse Short circuit protection of load and module Overvoltage protection at module input Open circuit protection without battery Reverse current protection at n...

Страница 2: ...User and Operation manual Specially designed for hybrid systems and telecommunications Steca Solarix 2401 4401 716 148 Z02 09_45 PHOTOVOLTAIK PHOTOVOLTAIC PHOTOVOLTAIQUE FOTOVOLTAICA EN...

Страница 3: ...3 Sub Menu 8 6 Installation 10 6 1 Precautions 10 6 2 Location Of Installation 10 6 2 1 Installation On Walls 11 6 2 2 Rules for mounting the System Manager 11 6 3 Preparations 11 6 3 1 Assemblies 11...

Страница 4: ...g on the PV system Before you start work Read the chapter Installation chapter 6 page 10 Make sure that all Precautions chapter 6 1 page 10 are taken Only start to install your System Manager when you...

Страница 5: ...by manufacturer are connected to this System Manager the user has to accept the consequences CAUTION Opening the System Manager connecting cover excluded as well as use other than prescribed by the m...

Страница 6: ...stem is set for use with lead accumulators batteries with liquid electrolyte and can be set for accumulators with fixed electrolyte like gel batteries The System Manager can be used for all types of s...

Страница 7: ...e corresponding final voltages If the Boost Charge voltage level is too high in comparison with the module voltage reduced by wire losses the countdown may never be started and your battery is therefo...

Страница 8: ...through the controller I_mod is the charging current produced by the solar modules When the voltage of the battery is getting near the final charge voltage the module current I_mod is substantially hi...

Страница 9: ...s can be changed by this scrolling action By pressing OK the displayed menu window is activated and the value is indicated Pressing OK once again leads to a closure of the window without adjustment Af...

Страница 10: ...V 30 0V 54 0V 60 0V The equalisation charging can be programmed similar to adjusting the boost charging Press OK to enter edit the equalisation charge voltage by pressing the arrow keys and confirm se...

Страница 11: ...PV system s efficiency and performance The solar PV array should be installed in a way that in the most unfavourable case the voltage drop is not so high that the battery can not be charged completel...

Страница 12: ...Make sure that the heat sink is well ventilated when mounting 6 3 Preparations 6 3 1 Assemblies Before installation lay out all cables junction boxes and safety fuses cut into sections isolate on both...

Страница 13: ...s to the System Manager s battery connection terminals the symbol shows a rectangular battery with and indicators and tighten securely with a proper slot screwdriver Pay attention to the right polarit...

Страница 14: ...In addition to the electronic fuse device mentioned above the System Manager has also been protected by regular fuses which have been rated far beyond nominal currents to prevent false blowing of the...

Страница 15: ...round for all system components All plus connections are internally connected anyway in the System Manager 6 7 2 Negative Grounding If Negative Grounding is used only one minus connection from any one...

Страница 16: ...ssible so that unnecessary costs can be avoided Certainly not all errors are listed below You will find the most common errors and symptoms covering the major part of all possible errors Send in the S...

Страница 17: ...ischarged deeply or increase solar array to add energy to the system Connect all loads through the System Manager to avoid strong discharge of the battery No module is connected otherwise module modul...

Страница 18: ...aired nor replaced or if this does not occur within a suitable period in spite of the specification of an extension period in writing by the customer the reduction in value caused by the fault shall b...

Страница 19: ......

Страница 20: ......

Страница 21: ...716148...

Отзывы: