background image

6.2.1  Installation On Walls 

The System-Manager has to be mounted on fire-proof surface. Furthermore, no flammable material should be allowed 
under the place where the System-Manager is mounted. 

The System-Manager is to be installed on vertical walls. This is the only way that the 
System-Manager can be cooled by naturally rising air (chimney effect) and work 
correctly. 

The System-Manager is screwed to the wall with the four holes drilled into the heat sink 
flanges. The System-Manager is designed without an integrated strain relief, so that the unit 
can be adapted to the prevailing conditions of various types of installations. For this reason, 
you must install a strain relief (e. g. cable clips) approx. 200 mm below the System-
Manager before the cables spread out to the individual components. 

When the System-Manager is in operation,  the high currents being regulated by the System-
Manager warm up the heat sink and air naturally rising past the heat sink fins extracts the 
heat. This chimney effect is necessary for proper cooling and System-Manager operation. 
Do not confine the System-Manager in a closed space, since this would make 
ventilation and cooling impossible. Adhere to a safety distance of min. 200 mm 
below and above the unit. 

After screwing the System-Manager to the wall, you can start wiring. 

6.2.2  Rules for mounting the System-Manager 

The System-Manager must be installed with cable openings down. 

For marking the mounting holes use the System-Manager as a stencil, but never as a stencil for 
drilling! 

Make sure that the heat sink is well ventilated when mounting. 

6.3  Preparations 

6.3.1  Assemblies 

Before installation, lay out all cables, junction boxes and safety fuses: 

  cut into sections 

  isolate on both sides and press on end sleeves for strands 

  prepare junction boxes 

6.3.2  Preparation Of Wiring 

Wires that are not permanently connected to the building must be strain-relieved outside the 
System-Manager! 

Please make sure that the wire diameter is in accordance with the System-Manager’s expected currents. The following 
table states the minimum cross sections that are necessary for constant currents that may occur during a period of time 
of approx. 30 min. This chart will allow the maximum distance from System-Manager to PV array junction box  of approx. 
10m; to battery approx. 2m; and to load distribution box approx. 5m. 
Before wiring, please check if the batteries are the right type 
and size, and always double check if they are connected to the 
System-Manager in the right polarity with a voltmeter, and it is 
a good idea to check battery bank voltage with voltmeter! Also 
make sure that the solar PV array’s maximum solar PV array 
current does not exceed the specifications of the System-
Manager. 

Current diameter AWG Isolation 

20A 10mm²  8  85°C 

30A 16mm²  6  85°C 

40A 16mm²  6  85°C 

50A 25mm²  4  85°C 

6.3.3  Cabling 

Solar PV modules create current whenever light strikes them. The current created varies with the light intensity, but even 
in the case of low levels of light, full voltage is given by the modules. Always cover the solar modules with an opaque lid 
that is fixed with tape while working on the PV array wiring or joining to the System-Manager. Due to this cover, the 

System-Manager  TAROM | 716148 

page 11 

V09_45A 

Содержание Solarix 2401

Страница 1: ...on by internal fuse Automatic electronic fuse Short circuit protection of load and module Overvoltage protection at module input Open circuit protection without battery Reverse current protection at n...

Страница 2: ...User and Operation manual Specially designed for hybrid systems and telecommunications Steca Solarix 2401 4401 716 148 Z02 09_45 PHOTOVOLTAIK PHOTOVOLTAIC PHOTOVOLTAIQUE FOTOVOLTAICA EN...

Страница 3: ...3 Sub Menu 8 6 Installation 10 6 1 Precautions 10 6 2 Location Of Installation 10 6 2 1 Installation On Walls 11 6 2 2 Rules for mounting the System Manager 11 6 3 Preparations 11 6 3 1 Assemblies 11...

Страница 4: ...g on the PV system Before you start work Read the chapter Installation chapter 6 page 10 Make sure that all Precautions chapter 6 1 page 10 are taken Only start to install your System Manager when you...

Страница 5: ...by manufacturer are connected to this System Manager the user has to accept the consequences CAUTION Opening the System Manager connecting cover excluded as well as use other than prescribed by the m...

Страница 6: ...stem is set for use with lead accumulators batteries with liquid electrolyte and can be set for accumulators with fixed electrolyte like gel batteries The System Manager can be used for all types of s...

Страница 7: ...e corresponding final voltages If the Boost Charge voltage level is too high in comparison with the module voltage reduced by wire losses the countdown may never be started and your battery is therefo...

Страница 8: ...through the controller I_mod is the charging current produced by the solar modules When the voltage of the battery is getting near the final charge voltage the module current I_mod is substantially hi...

Страница 9: ...s can be changed by this scrolling action By pressing OK the displayed menu window is activated and the value is indicated Pressing OK once again leads to a closure of the window without adjustment Af...

Страница 10: ...V 30 0V 54 0V 60 0V The equalisation charging can be programmed similar to adjusting the boost charging Press OK to enter edit the equalisation charge voltage by pressing the arrow keys and confirm se...

Страница 11: ...PV system s efficiency and performance The solar PV array should be installed in a way that in the most unfavourable case the voltage drop is not so high that the battery can not be charged completel...

Страница 12: ...Make sure that the heat sink is well ventilated when mounting 6 3 Preparations 6 3 1 Assemblies Before installation lay out all cables junction boxes and safety fuses cut into sections isolate on both...

Страница 13: ...s to the System Manager s battery connection terminals the symbol shows a rectangular battery with and indicators and tighten securely with a proper slot screwdriver Pay attention to the right polarit...

Страница 14: ...In addition to the electronic fuse device mentioned above the System Manager has also been protected by regular fuses which have been rated far beyond nominal currents to prevent false blowing of the...

Страница 15: ...round for all system components All plus connections are internally connected anyway in the System Manager 6 7 2 Negative Grounding If Negative Grounding is used only one minus connection from any one...

Страница 16: ...ssible so that unnecessary costs can be avoided Certainly not all errors are listed below You will find the most common errors and symptoms covering the major part of all possible errors Send in the S...

Страница 17: ...ischarged deeply or increase solar array to add energy to the system Connect all loads through the System Manager to avoid strong discharge of the battery No module is connected otherwise module modul...

Страница 18: ...aired nor replaced or if this does not occur within a suitable period in spite of the specification of an extension period in writing by the customer the reduction in value caused by the fault shall b...

Страница 19: ......

Страница 20: ......

Страница 21: ...716148...

Отзывы: