HARD WATER

Where hard water conditions exist, water softening or the threshold 

type of water treatment is recommended.  This will protect the 

dishwashers, coffee urns, water heaters, water piping and other 

equipment.

See  MAINTENANCE  section  for  details  of  tank  cleanout 

procedure.

AIR REQUIREMENTS

REFER TO THE CURRENT EDITION OF THE “NATIONAL FUEL 

GAS CODE” ANSI Z223.1/NFPA 54.

 

WARNING

KEEP APPLIANCE AREA CLEAR AND FREE OF COMBUSTIBLE 

MATERIALS, GASOLINE AND OTHER FLAMMABLES, VAPORS 

AND LIQUIDS.

DO  NOT  OBSTRUCT  THE  FLOW  OF  COMBUSTION  OR 

VENTILATING AIR.

 

WARNING

FOR  SAFE  OPERATION  PROVIDE ADEQUATE AIR  FOR 

COMBUSTION AND VENTILATION.  AN INSUFFICIENT SUPPLY 

OF AIR  WILL  CAUSE  RECIRCULATION  OF  COMBUSTION 

PRODUCTS  RESULTING  IN AIR  CONTAMINATION  THAT 

MAY BE HAZARDOUS TO LIFE.  SUCH A CONDITION OFTEN 

WILL  RESULT  IN A YELLOW,  LUMINOUS  BURNER  FLAME, 

CAUSING CARBONING OR SOOTING OF THE COMBUSTION 

CHAMBER,  BURNERS AND  FLUE TUBES AND  CREATES A 

RISK OF ASPHYXIATION.

Where  an  exhaust  fan  is  supplied  in  the  same  room  with 

a  heater,  sufficient  openings  for  air  must  be  provided  in 

the  walls.   

UNDERSIZED OPENINGS WILL CAUSE AIR TO 

BE  DRAWN  INTO  THE  ROOM  THROUGH  THE  CHIMNEY, 

CAUSING POOR COMBUSTION. SOOTING MAY RESULT IN 

SERIOUS DAMAGE TO THE HEATER AND RISK OF FIRE OR 

EXPLOSION.

UNCONFINED SPACE

In buildings of conventional frame, brick, or stone construction, 

unconfined  spaces  may  provide  adequate  air  for  combustion, 

ventilation and draft hood dilution.

If the unconfined space is within a building of tight construction 

(buildings  using  the  following  construction:  weather  stripping, 

heavy insulation, caulking, vapor barrier, etc.), air for combustion, 

ventilation and draft hood dilution must be obtained from outdoors.  

The  installation  instructions  for  confined  spaces  in  tightly 

constructed buildings must be followed to ensure adequate air 

supply.

CONFINED SPACE

When  drawing  combustion  and  dilution  air  from  inside  a 

conventionally constructed building to a confined space, such a 

space shall be provided with two permanent openings, ONE IN OR 

WITHIN 12 INCHES (30.5cm) OF THE ENCLOSURE TOP AND 

ONE IN OR WITHIN 12 INCHES (30.5cm) OF THE ENCLOSURE 

BOTTOM.  Each opening shall have a free area of at least one 

square inch per 1000 Btuh (2,225mm

2

/kW) of the total input of all 

appliances in the enclosure, but not less than 100 square inches 

(645 square cm).

If  the  confined  space  is  within  a  building  of  tight  construction, 

air for combustion, ventilation, and draft hood dilution must be 

obtained from outdoors.  When directly communicating with the 

outdoors  or  communicating  with  the  outdoors  through  vertical 

ducts, two permanent openings, located in the above manner, 

shall be provided.  Each opening shall have a free area of not 

less than one square inch per 4000 Btuh (8,900mm

2

/kW) of the 

total input of all appliances in the enclosure.  If horizontal ducts 

are used, each opening shall have a free area of not less than 

one square inch per 2000 Btuh (4,450mm

2

/kW) of the total input 

of all appliances in the enclosure. 

VENT REDUCER

The SBD 250, 251, and 275 models are shipped with an 8” to 

6” diameter flue outlet adapter. Each adapter fits on top of the 

installed flue damper.  Use only vent reducers supplied with the 

unit.  The venting must comply with the NATIONAL FUEL GAS 

CODE, ANSI Z223.1/NFPA 54.

FIGURE 7

 ILLUSTRATION OF MINIMUM COMBUSTIBLE CLEARANCES IN AN ALCOVE

FIGURE 6

Содержание SBD100199*

Страница 1: ...FERENCE CAUTION TEXT PRINTED OR OUTLINED IN RED CONTAINS INFORMATION RELATIVE TO YOUR SAFETY PLEASE READ THOROUGHLY BEFORE INSTALLING AND USING THIS APPLIANCE Thank you for buying this energy efficien...

Страница 2: ...FIGURE 1 ROUGH IN DIMENSIONS See Tables 1A and 1B SBD71120 models are approved for 5 13 cm venting using a 6 15 cm to 5 13 cm reducer...

Страница 3: ...5 NA 1 50 1 50 NA 1 50 1 50 750 Lbs 862 Lbs 89 kW Hr 246 L 191 cm 12 cm 167 cm 145 cm 51 cm NA 1 2 149 cm 20 cm 70 cm NA 1 50 1 50 NA 1 50 1 50 341 Kg 391 Kg SBD85365 365 000 BTR Hr 85 Gal 79 50 4 50...

Страница 4: ...89 kWh 365 000 107 kWh 399 000 117 kWh and 500 000 147 kWh Btuh with a recovery rating of 277 3 gph 1049 Lph or more also comply with ANSI Z21 10 3 as an automatic instantaneous type heater Detailed...

Страница 5: ...such as having a cold or diminishing sense of smell with age For these reasons the use of a propane gas detector is recommended IF YOU EXPERIENCE AN OUT OF GAS SITUATION DO NOT TRYTO RELIGHTAPPLIANCE...

Страница 6: ...cannon must be oriented correctly for proper function There is a marked range on the pipe nipple portion of the hydro cannon that must be aligned with the top of the inlet spud A label above the jacke...

Страница 7: ...d with commercial water heaters Although circulators are oiled and operated by the manufacturer some circulators must be oiled again before operating Please refer to manufacturer s instructions DISHWA...

Страница 8: ...t least 2 5cm deep with length and width at least 2 5cm greater than the diameter of the heater and must be piped to an adequate drain The pan must not restrict combustion air flow For appliance insta...

Страница 9: ...insulation caulking vapor barrier etc air for combustion ventilation and draft hood dilution must be obtained from outdoors The installation instructions for confined spaces in tightly constructed bui...

Страница 10: ...ere will be a minimum of turbulence inside the heater If a water heater is installed in a closed water system contact the water supplier or local plumbing inspector on how to control this situation WA...

Страница 11: ...0 197 198 199 200 Input 180 000 190 000 199 000 Btuh Total Vent Height Feet Draft Hood 6 6 8 10 15 20 30 50 100 Input Btuh Rise Vent Connector Diameter in inches 180 000 1 Ft 8 8 8 8 8 7 7 7 190 000 8...

Страница 12: ...10 10 8 8 8 Number of Combined Input Heaters in Thousands of Btuh Manifold Common Vent Diameter 2 610 14 14 12 12 12 10 10 10 3 915 16 16 16 14 14 12 12 12 4 1220 18 18 16 16 16 14 14 12 MODEL 365 40...

Страница 13: ...0 60 66 138 260 530 810 1520 2400 4300 8800 70 61 125 240 490 750 1400 2250 3900 8100 80 57 118 220 460 690 1300 2050 3700 7500 90 53 110 205 430 650 1220 1950 3450 7200 100 50 103 195 400 620 1150 18...

Страница 14: ...input adjustment must not be less than 4 5 W C 1 12 Kpa for natural gas and 11 0 W C 2 74 Kpa for propane gas FIGURE 11 Do not subject the combination gas valve to inlet gas pressures of more than 14...

Страница 15: ...Install in accordance with all local codes Use of the top inlet water connection requires installation of an inlet dip tube refer to figure 12 The tube is supplied in the heater Follow caution labels...

Страница 16: ...OULD NOT EXCEED SAFE USE TEMPERATUREATFIXTURES SEEWATERTEMPERATURECONTROL WARNING ON PAGE 27 IF HIGHER PREHEAT TEMPERATURES ARE NECESSARY TO OBTAIN ADEQUATE BOOSTER OUTPUT ADD AN ANTI SCALD VALVE FOR...

Страница 17: ...ED ON DURING THE RINSE OPERATION AND OPEN OFF WHEN DISHWASHER IS NOT OPERATING OR WHEN ON LONG STANDBY NOTE 2 INSTALL LINE TEMPERATURE CONTROL IN AN UNINSULATED TEE BEYOND THE DISHWASHING MACHINE TAKE...

Страница 18: ...nstallation diagrams on the following pages are typical TWO TEMPERATURE TWO HEATERS ONE PRE HEATER ONE BOOSTER HEATER WITH OR WITHOUT BUILDING RECIRCULATION The discharge opening of the temperature an...

Страница 19: ...TE 3 ADJUST PLUG COCK SO THE SANITIZING LOOP FLOW RATE DOES NOT CAUSE UNNECESSARY TURBULENCE IN THE TANK PIPE RELIEF VALVE TO OPEN DRAIN INSTALL IN ACCORDANCE WITH LOCAL CODES CIRCULATING RETURN LINE...

Страница 20: ...GHER PREHEAT TEMPERATURESARE NECESSARY TO OBTAIN ADEQUATE BOOSTER OUTPUT ADDANANTI SCALD VALVE FOR HOT WATER SUPPLIED TO FIXTURES INSERT A CAUTION IF BUILDING COLD WATER SUPPLY HAS A BACKFLOW PREVENTE...

Страница 21: ...OOSTER OUTPUT ADD AN ANTI SCALD VALVE FOR HOT WATER SUPPLIED TO FIXTURES PIPE RELIEF VALVE TO OPEN DRAIN WHEN USING A STATE T 140 200 350 OR 400 STORAGE TANK USE LOWER 3 4 OPENING FOR TANK TEMPERATURE...

Страница 22: ...ANIFOLD KIT PART NO 78694 DIMENSIONS A INCHES CM MODEL LOW PROFILE VERTICAL HOOD A SBD MODELS 120 69 75 177cm 154 73 00 185cm 180 67 50 171cm 197 75 00 192cm 198 75 00 192cm 199 67 50 171cm 200 72 00...

Страница 23: ...tallations contact State Water Heaters Technical Support Center at 1 800 527 1953 TABLE 5 MANIFOLD GAS PRESSURE IN INCHES OF WATER COLUMN ALL MODELS TYPE OF GAS NATURAL PROPANE 3 5 10 0 Gas pressure s...

Страница 24: ...PURGE DISCHARGE MUST NOT ENTER CONFINEDAREASORSPACESWHEREIGNITIONCANOCCUR THE AREA MUST BE WELL VENTILATED AND ALL SOURCES OF IGNITION MUST BE INACTIVATED OR REMOVED WARNING THE GAS VALVE MUST HAVE B...

Страница 25: ...25 FOR NATURAL GAS MODELS FOR YOUR SAFETY READ BEFORE OPERATING OPERATING INSTRUCTIONS FOR YOUR SAFETY READ BEFORE OPERATING...

Страница 26: ...26 FOR PROPANE GAS MODELS FOR YOUR SAFETY READ BEFORE OPERATING OPERATING INSTRUCTIONS TO TURN OFF GAS TO THE APPLIANCE...

Страница 27: ...the damper disc manually or motor damage will occur If the water heater does not operate with the Service Switch in either position Refer to the Troubleshooting Sections and Operational Checklist sec...

Страница 28: ...REVENTIVE MAINTENANCE CHECK THE PILOT At least once a year check the pilot burner fig 14 and the main burner fig 15 for proper operation Refer to the following pilot and main burner sections PILOT BUR...

Страница 29: ...a manometer to the gauge port and refer to Table 5 for correct manifold pressure 2 Use this formula to clock the meter Be sure that other gas consuming appliances are not operating during this interva...

Страница 30: ...heater and replacement of the factory installed magnesium anodes with aluminum anodes may correct the condition Occasionally water softener companies recommend removal of heater anodes for odor reason...

Страница 31: ...d screws securing tank cleanout plate and remove plate 4 Remove lime scale or sediment using care not to damage the glass lining 5 Inspect cleanout plate gasket if new gasket is required replace with...

Страница 32: ...ed by the UN LIME it can be reused if not the UN LIME should be replaced TROUBLESHOOTING IGNITION MODULE SYSTEM Before calling your service agent the following checklist should be examined to eliminat...

Страница 33: ...breaker 5 Disconnect switch off 6 Harness not plugged into appliance receptacle A FLUE DAMPER OPEN OR OPENING Unit is calling for heat and damper disc should be in vertical position VOLTAGE ACROSS 4...

Страница 34: ...slower Call serviceman Check gas input If incorrect adjust gas pressure or replace main burner orifice Draft hood not installed or Call serviceman Install draft hood or baffles as one or more flue ba...

Страница 35: ...35...

Страница 36: ...36 500 Tennessee Waltz Parkway Ashland City TN 37015 Phone 800 365 0024 Fax 800 644 9306 www statewaterheaters com...

Отзывы: