VENTING

 WARNING

THE INSTRUCTIONS IN THIS SECTION ON VENTING MUST 

BE FOLLOWED TO AVOID CHOKED COMBUSTION OR RE-

CIRCULATION OF FLUE GASES.  SUCH CONDITIONS CAUSE 

SOOTING OR RISKS OF FIRE AND ASPHYXIATION.

Heater must be protected from freezing downdrafts.

Remove all soot or other obstructions from the chimney that will 

retard a free draft.

Type B venting is recommended with these heaters. See table 3  

TECHNICAL DATA VENTING. 

This  water  heater  must  be  vented  in  compliance  with  all  local 

codes, the current edition of the National Fuel Gas Code (ANSI-

Z223.1) and with the Category I Venting Tables.

If  any  parts  of  the  vent  system  are  exposed  to  ambient 

temperatures below 35 degrees F (2 degrees C) they must be 

insulated to prevent condensation.

•  Do not connect the heater to a common vent or chimney with 

solid fuel burning equipment.  This practice is prohibited by 

many local  building codes as is the practice of venting gas 

fired equipment to the duct work of ventilation systems.

•  Where  a  separate  vent  connection  is  not  available  and  the 

vent pipe from the heater must be connected to a common 

vent with an oil burning furnace, the vent pipe should enter the 

smaller common vent or chimney at a point above the large 

vent pipe.

FIGURE 8

MULTIPLE HEATER MANIFOLD

Figure 9 and table 3 should be used for horizontally manifolding two 

or more heaters. Also see MULTIPLE-UNIT INSTALLATIONS of 

MECHANICAL VENTING section for induced draft applications.

FIGURE 9

WATER LINE CONNECTIONS

This manual provides detailed installation diagrams (see pages

 

16-22 of this manual) for typical methods of application for the 

water heaters.
The water heater may be installed by itself, or with a separate

 

storage  tank,  on  both  single  and  two-temperature  systems.  

When  used  with  a  separate  storage  tank,  the  circulation  may 

be either by gravity or by means of a circulating pump.  When a 

circulating pump is used it is important to note that the flow rate 

should be slow so that there will be a minimum of turbulence 

inside the heater.
If a water heater is installed in a closed water system, contact 

the water supplier or local plumbing inspector on how to control 

this situation.

WATER (POTABLE) HEATING AND 

SPACE HEATING 

1.  All piping components connected to this unit for space heating 

applications shall be suitable for use with potable water.

2.  Toxic chemicals, such as those used for boiler treatment, shall 

NEVER be introduced into this system.

3.  This unit may NEVER be connected to any existing heating

  system or component(s) previously used with a non-potable

  water heating appliance.

4.  When  the  system  requires  water  for  space  heating  at 

temperatures higher than required for domestic water purposes, 

a tempering valve must be installed.  Please refer to installation 

diagrams on pages 16 through 22 in this manual for suggested 

piping arrangements.

 CAUTION

A  closed  system  will  exist  if  a  check  valve  (without  bypass), 

pressure reducing valve (without bypass), or a water meter (without 

bypass) is installed in the cold water line between the water heater 

and street main (or well).

Excessive pressure may develop in such closed systems, causing 

premature tank failure or intermittent relief valve operation.  

This 

is not a warranty failure.  An expansion tank or a similar device 

may be required in the inlet supply line between the appliance 

and the meter or valve to compensate

 

for the thermal expansion 

of the water.

SYSTEM CONNECTIONS

The system installation must conform to these instructions and to 

the local code authority having jurisdiction.  Good practice requires 

that all heavy piping be supported.

THERMOMETERS (Not Supplied)

Thermometers should be obtained and field installed as shown in 

the installation diagrams.

Thermometers are installed in the system as a means of detecting 

the temperature of the outlet water supply.

RELIEF VALVE

This water heater is equipped with a combination temperature-

pressure relief valve that complies with the standard for relief 

valves and automatic gas shutoff devices for hot water supply 

system, ANSI Z21.22. 

FOR SAFE OPERATION OF THE WATER 

HEATER, THE  RELIEF  VALVE(S)  MUST  NOT  BE  REMOVED 

OR PLUGGED.

Содержание SBD100199*

Страница 1: ...FERENCE CAUTION TEXT PRINTED OR OUTLINED IN RED CONTAINS INFORMATION RELATIVE TO YOUR SAFETY PLEASE READ THOROUGHLY BEFORE INSTALLING AND USING THIS APPLIANCE Thank you for buying this energy efficien...

Страница 2: ...FIGURE 1 ROUGH IN DIMENSIONS See Tables 1A and 1B SBD71120 models are approved for 5 13 cm venting using a 6 15 cm to 5 13 cm reducer...

Страница 3: ...5 NA 1 50 1 50 NA 1 50 1 50 750 Lbs 862 Lbs 89 kW Hr 246 L 191 cm 12 cm 167 cm 145 cm 51 cm NA 1 2 149 cm 20 cm 70 cm NA 1 50 1 50 NA 1 50 1 50 341 Kg 391 Kg SBD85365 365 000 BTR Hr 85 Gal 79 50 4 50...

Страница 4: ...89 kWh 365 000 107 kWh 399 000 117 kWh and 500 000 147 kWh Btuh with a recovery rating of 277 3 gph 1049 Lph or more also comply with ANSI Z21 10 3 as an automatic instantaneous type heater Detailed...

Страница 5: ...such as having a cold or diminishing sense of smell with age For these reasons the use of a propane gas detector is recommended IF YOU EXPERIENCE AN OUT OF GAS SITUATION DO NOT TRYTO RELIGHTAPPLIANCE...

Страница 6: ...cannon must be oriented correctly for proper function There is a marked range on the pipe nipple portion of the hydro cannon that must be aligned with the top of the inlet spud A label above the jacke...

Страница 7: ...d with commercial water heaters Although circulators are oiled and operated by the manufacturer some circulators must be oiled again before operating Please refer to manufacturer s instructions DISHWA...

Страница 8: ...t least 2 5cm deep with length and width at least 2 5cm greater than the diameter of the heater and must be piped to an adequate drain The pan must not restrict combustion air flow For appliance insta...

Страница 9: ...insulation caulking vapor barrier etc air for combustion ventilation and draft hood dilution must be obtained from outdoors The installation instructions for confined spaces in tightly constructed bui...

Страница 10: ...ere will be a minimum of turbulence inside the heater If a water heater is installed in a closed water system contact the water supplier or local plumbing inspector on how to control this situation WA...

Страница 11: ...0 197 198 199 200 Input 180 000 190 000 199 000 Btuh Total Vent Height Feet Draft Hood 6 6 8 10 15 20 30 50 100 Input Btuh Rise Vent Connector Diameter in inches 180 000 1 Ft 8 8 8 8 8 7 7 7 190 000 8...

Страница 12: ...10 10 8 8 8 Number of Combined Input Heaters in Thousands of Btuh Manifold Common Vent Diameter 2 610 14 14 12 12 12 10 10 10 3 915 16 16 16 14 14 12 12 12 4 1220 18 18 16 16 16 14 14 12 MODEL 365 40...

Страница 13: ...0 60 66 138 260 530 810 1520 2400 4300 8800 70 61 125 240 490 750 1400 2250 3900 8100 80 57 118 220 460 690 1300 2050 3700 7500 90 53 110 205 430 650 1220 1950 3450 7200 100 50 103 195 400 620 1150 18...

Страница 14: ...input adjustment must not be less than 4 5 W C 1 12 Kpa for natural gas and 11 0 W C 2 74 Kpa for propane gas FIGURE 11 Do not subject the combination gas valve to inlet gas pressures of more than 14...

Страница 15: ...Install in accordance with all local codes Use of the top inlet water connection requires installation of an inlet dip tube refer to figure 12 The tube is supplied in the heater Follow caution labels...

Страница 16: ...OULD NOT EXCEED SAFE USE TEMPERATUREATFIXTURES SEEWATERTEMPERATURECONTROL WARNING ON PAGE 27 IF HIGHER PREHEAT TEMPERATURES ARE NECESSARY TO OBTAIN ADEQUATE BOOSTER OUTPUT ADD AN ANTI SCALD VALVE FOR...

Страница 17: ...ED ON DURING THE RINSE OPERATION AND OPEN OFF WHEN DISHWASHER IS NOT OPERATING OR WHEN ON LONG STANDBY NOTE 2 INSTALL LINE TEMPERATURE CONTROL IN AN UNINSULATED TEE BEYOND THE DISHWASHING MACHINE TAKE...

Страница 18: ...nstallation diagrams on the following pages are typical TWO TEMPERATURE TWO HEATERS ONE PRE HEATER ONE BOOSTER HEATER WITH OR WITHOUT BUILDING RECIRCULATION The discharge opening of the temperature an...

Страница 19: ...TE 3 ADJUST PLUG COCK SO THE SANITIZING LOOP FLOW RATE DOES NOT CAUSE UNNECESSARY TURBULENCE IN THE TANK PIPE RELIEF VALVE TO OPEN DRAIN INSTALL IN ACCORDANCE WITH LOCAL CODES CIRCULATING RETURN LINE...

Страница 20: ...GHER PREHEAT TEMPERATURESARE NECESSARY TO OBTAIN ADEQUATE BOOSTER OUTPUT ADDANANTI SCALD VALVE FOR HOT WATER SUPPLIED TO FIXTURES INSERT A CAUTION IF BUILDING COLD WATER SUPPLY HAS A BACKFLOW PREVENTE...

Страница 21: ...OOSTER OUTPUT ADD AN ANTI SCALD VALVE FOR HOT WATER SUPPLIED TO FIXTURES PIPE RELIEF VALVE TO OPEN DRAIN WHEN USING A STATE T 140 200 350 OR 400 STORAGE TANK USE LOWER 3 4 OPENING FOR TANK TEMPERATURE...

Страница 22: ...ANIFOLD KIT PART NO 78694 DIMENSIONS A INCHES CM MODEL LOW PROFILE VERTICAL HOOD A SBD MODELS 120 69 75 177cm 154 73 00 185cm 180 67 50 171cm 197 75 00 192cm 198 75 00 192cm 199 67 50 171cm 200 72 00...

Страница 23: ...tallations contact State Water Heaters Technical Support Center at 1 800 527 1953 TABLE 5 MANIFOLD GAS PRESSURE IN INCHES OF WATER COLUMN ALL MODELS TYPE OF GAS NATURAL PROPANE 3 5 10 0 Gas pressure s...

Страница 24: ...PURGE DISCHARGE MUST NOT ENTER CONFINEDAREASORSPACESWHEREIGNITIONCANOCCUR THE AREA MUST BE WELL VENTILATED AND ALL SOURCES OF IGNITION MUST BE INACTIVATED OR REMOVED WARNING THE GAS VALVE MUST HAVE B...

Страница 25: ...25 FOR NATURAL GAS MODELS FOR YOUR SAFETY READ BEFORE OPERATING OPERATING INSTRUCTIONS FOR YOUR SAFETY READ BEFORE OPERATING...

Страница 26: ...26 FOR PROPANE GAS MODELS FOR YOUR SAFETY READ BEFORE OPERATING OPERATING INSTRUCTIONS TO TURN OFF GAS TO THE APPLIANCE...

Страница 27: ...the damper disc manually or motor damage will occur If the water heater does not operate with the Service Switch in either position Refer to the Troubleshooting Sections and Operational Checklist sec...

Страница 28: ...REVENTIVE MAINTENANCE CHECK THE PILOT At least once a year check the pilot burner fig 14 and the main burner fig 15 for proper operation Refer to the following pilot and main burner sections PILOT BUR...

Страница 29: ...a manometer to the gauge port and refer to Table 5 for correct manifold pressure 2 Use this formula to clock the meter Be sure that other gas consuming appliances are not operating during this interva...

Страница 30: ...heater and replacement of the factory installed magnesium anodes with aluminum anodes may correct the condition Occasionally water softener companies recommend removal of heater anodes for odor reason...

Страница 31: ...d screws securing tank cleanout plate and remove plate 4 Remove lime scale or sediment using care not to damage the glass lining 5 Inspect cleanout plate gasket if new gasket is required replace with...

Страница 32: ...ed by the UN LIME it can be reused if not the UN LIME should be replaced TROUBLESHOOTING IGNITION MODULE SYSTEM Before calling your service agent the following checklist should be examined to eliminat...

Страница 33: ...breaker 5 Disconnect switch off 6 Harness not plugged into appliance receptacle A FLUE DAMPER OPEN OR OPENING Unit is calling for heat and damper disc should be in vertical position VOLTAGE ACROSS 4...

Страница 34: ...slower Call serviceman Check gas input If incorrect adjust gas pressure or replace main burner orifice Draft hood not installed or Call serviceman Install draft hood or baffles as one or more flue ba...

Страница 35: ...35...

Страница 36: ...36 500 Tennessee Waltz Parkway Ashland City TN 37015 Phone 800 365 0024 Fax 800 644 9306 www statewaterheaters com...

Отзывы: