30

VENTING SYSTEM

Examine the venting system every six months for obstructions

 

and/or deterioration of the vent piping.

Remove all soot or other obstructions from chimney which will

 

retard free draft.

REMOTE STORAGE TANK 

TEMPERATURE CONTROL

The water temperature in the storage tank (if used) is controlled

 

by the storage tank temperature control.  The sensing element is 

mounted in the hot water storage tank, see page 17.
A change in water temperature in the storage tank lower than 

the

  tank  temperature  control  setting  will  cause  the  sensor  to 

activate the circulating pump.  The pump then circulates the water 

through the heater where the thermostat senses the drop in water 

temperature and activates main burner operation of the appliance.

If the storage tank temperature control is out of calibration, replace 

with new control.

 WARNING

SHOULD OVERHEATING OCCUR OR THE GAS SUPPLY FAIL 

TO SHUT OFF, TURN OFF THE MANUAL GAS CONTROL VALVE 

TO THE APPLIANCE.

RELIEF VALVE

At least once a year, the temperature and pressure relief valve

 

should be checked to ensure that it is in operating condition.  Lift 

the lever at the top of the valve several times until the valve seats 

properly and operates freely.

If the appliance installation includes other relief valves, such as

 

in “remote” storage tanks etc., check their relief valve operation 

with the same frequency.

 WARNING

THE  WATER  PASSING  OUT  OF THE  VALVE  DURING THIS 

CHECKING OPERATION MAY BE EXTREMELY HOT.  AVOID 

CONTACT AND DISCHARGE SAFELY TO PREVENT WATER 

DAMAGE.

If  the  temperature  and  pressure  relief  valve  on  the  heater

 

discharges periodically or continuously, a problem exists.  This 

may be due to unusually high water temperatures or pressures 

in the system, or to a faulty relief valve.  Contact your dealer or a 

qualified service technician to find the cause of the problem and to 

correct it.  This may also be due to thermal expansion in a closed 

water supply system.  Contact the water supplier or local plumbing 

inspector on how to correct this situation.  

DO NOT PLUG THE 

TEMPERATURE AND PRESSURE RELIEF VALVE.

 WARNING

SHOULD OVERHEATING OCCUR OR THE GAS SUPPLY FAIL 

TO SHUT OFF, TURN OFF THE MANUAL GAS CONTROL VALVE 

TO THE APPLIANCE.

HOT  WATER ODOR

On occasion, hot water may develop a strong odor.  If this occurs 

drain  the  heater  completely,  flush  thoroughly,  and  refill.    If  the 

problem persists, chlorination of the heater and replacement of 

the factory installed magnesium anodes with aluminum anodes 

may correct the condition.

Occasionally water softener companies recommend removal of

 

heater anodes for odor reasons.

 

CAUTION

Unauthorized removal of the anode(s) will void the warranty.  For 

further information contact your dealer.

ANODE ROD INSPECTION

The heater tank is equipped with anode rods to provide corrosion 

control.  At least once a year the anode rods should be checked 

to determine if replacement is necessary.  Initially the anode rods 

are  approximately  7/8”  (22mm)  in  diameter  with  a  1/8”  (3mm) 

diameter steel core wire running down the center of the anode 

material.  THE ANODES SHOULD BE REPLACED when the 1/8” 

(3mm) diameter core wire is visible as this means that the  anode 

material has been expended in the control of corrosion.

For  models  with  top  inlet  and  outlet,  it  is  recommended  that, 

before  removing  the  inner  cover  for  cleaning,  inspection  or 

removal of inner parts, you obtain two new nipple collars, part no. 

74060.  The nipple collars on the heater will usually be damaged 

when removed.  New pipe collars will insure that the seal is such 

as to prevent leakage of flue products when properly installed.

NOTE:

 

 Anode rod inspection may need to be made more 

frequently  in  areas  subject  to  acid  rain  that  obtains  their 

water supply from surface water as the low pH will accelerate 

anode activity.

CAUTION:

 

  Close  cold  water  inlet  valve  serving  heater 

and  open  nearby  hot  water  faucet  to  relieve  the  pressure 

in  the  heater  before  attempting  to  remove  anode(s)  for 

inspection.

RECOMMENDED PROCEDURE FOR 

PERIODIC REMOVAL OF LIME DEPOSITS 

FROM TANK TYPE COMMERCIAL WATER 

HEATERS

The amount of calcium carbonate (lime) released from water is 

in direct proportion to water temperature and usage, see chart.  

The higher the water temperature or water usage, the more lime 

deposits are dropped out of the water.  This is the lime scale which 

forms in pipes, heaters and on cooking utensils.

Lime  accumulation  not  only  reduces  the  life  of  the  equipm

ent 

but  also  reduces  efficiency  of  the  heater  and  increases  fuel 

consumption.

The  usage  of  water  softening  equipment  greatly  reduces  the 

hardness  of  the  water.    However,  this  equipment  does  not 

always  remove  all  of  the  hardness  (lime).    For  this  reason 

it  is  recommended  that  a  regular  schedule  for  deliming  be 

maintained.

The  time  between  cleaning  will  vary  from  weeks  to  mon

ths 

depending upon water conditions and usage.

Refer to State booklet, Form No. 4800, entitled “Why? When and 

How” for detailed description on tank inspection and cleanout. 

Содержание SBD100199*

Страница 1: ...FERENCE CAUTION TEXT PRINTED OR OUTLINED IN RED CONTAINS INFORMATION RELATIVE TO YOUR SAFETY PLEASE READ THOROUGHLY BEFORE INSTALLING AND USING THIS APPLIANCE Thank you for buying this energy efficien...

Страница 2: ...FIGURE 1 ROUGH IN DIMENSIONS See Tables 1A and 1B SBD71120 models are approved for 5 13 cm venting using a 6 15 cm to 5 13 cm reducer...

Страница 3: ...5 NA 1 50 1 50 NA 1 50 1 50 750 Lbs 862 Lbs 89 kW Hr 246 L 191 cm 12 cm 167 cm 145 cm 51 cm NA 1 2 149 cm 20 cm 70 cm NA 1 50 1 50 NA 1 50 1 50 341 Kg 391 Kg SBD85365 365 000 BTR Hr 85 Gal 79 50 4 50...

Страница 4: ...89 kWh 365 000 107 kWh 399 000 117 kWh and 500 000 147 kWh Btuh with a recovery rating of 277 3 gph 1049 Lph or more also comply with ANSI Z21 10 3 as an automatic instantaneous type heater Detailed...

Страница 5: ...such as having a cold or diminishing sense of smell with age For these reasons the use of a propane gas detector is recommended IF YOU EXPERIENCE AN OUT OF GAS SITUATION DO NOT TRYTO RELIGHTAPPLIANCE...

Страница 6: ...cannon must be oriented correctly for proper function There is a marked range on the pipe nipple portion of the hydro cannon that must be aligned with the top of the inlet spud A label above the jacke...

Страница 7: ...d with commercial water heaters Although circulators are oiled and operated by the manufacturer some circulators must be oiled again before operating Please refer to manufacturer s instructions DISHWA...

Страница 8: ...t least 2 5cm deep with length and width at least 2 5cm greater than the diameter of the heater and must be piped to an adequate drain The pan must not restrict combustion air flow For appliance insta...

Страница 9: ...insulation caulking vapor barrier etc air for combustion ventilation and draft hood dilution must be obtained from outdoors The installation instructions for confined spaces in tightly constructed bui...

Страница 10: ...ere will be a minimum of turbulence inside the heater If a water heater is installed in a closed water system contact the water supplier or local plumbing inspector on how to control this situation WA...

Страница 11: ...0 197 198 199 200 Input 180 000 190 000 199 000 Btuh Total Vent Height Feet Draft Hood 6 6 8 10 15 20 30 50 100 Input Btuh Rise Vent Connector Diameter in inches 180 000 1 Ft 8 8 8 8 8 7 7 7 190 000 8...

Страница 12: ...10 10 8 8 8 Number of Combined Input Heaters in Thousands of Btuh Manifold Common Vent Diameter 2 610 14 14 12 12 12 10 10 10 3 915 16 16 16 14 14 12 12 12 4 1220 18 18 16 16 16 14 14 12 MODEL 365 40...

Страница 13: ...0 60 66 138 260 530 810 1520 2400 4300 8800 70 61 125 240 490 750 1400 2250 3900 8100 80 57 118 220 460 690 1300 2050 3700 7500 90 53 110 205 430 650 1220 1950 3450 7200 100 50 103 195 400 620 1150 18...

Страница 14: ...input adjustment must not be less than 4 5 W C 1 12 Kpa for natural gas and 11 0 W C 2 74 Kpa for propane gas FIGURE 11 Do not subject the combination gas valve to inlet gas pressures of more than 14...

Страница 15: ...Install in accordance with all local codes Use of the top inlet water connection requires installation of an inlet dip tube refer to figure 12 The tube is supplied in the heater Follow caution labels...

Страница 16: ...OULD NOT EXCEED SAFE USE TEMPERATUREATFIXTURES SEEWATERTEMPERATURECONTROL WARNING ON PAGE 27 IF HIGHER PREHEAT TEMPERATURES ARE NECESSARY TO OBTAIN ADEQUATE BOOSTER OUTPUT ADD AN ANTI SCALD VALVE FOR...

Страница 17: ...ED ON DURING THE RINSE OPERATION AND OPEN OFF WHEN DISHWASHER IS NOT OPERATING OR WHEN ON LONG STANDBY NOTE 2 INSTALL LINE TEMPERATURE CONTROL IN AN UNINSULATED TEE BEYOND THE DISHWASHING MACHINE TAKE...

Страница 18: ...nstallation diagrams on the following pages are typical TWO TEMPERATURE TWO HEATERS ONE PRE HEATER ONE BOOSTER HEATER WITH OR WITHOUT BUILDING RECIRCULATION The discharge opening of the temperature an...

Страница 19: ...TE 3 ADJUST PLUG COCK SO THE SANITIZING LOOP FLOW RATE DOES NOT CAUSE UNNECESSARY TURBULENCE IN THE TANK PIPE RELIEF VALVE TO OPEN DRAIN INSTALL IN ACCORDANCE WITH LOCAL CODES CIRCULATING RETURN LINE...

Страница 20: ...GHER PREHEAT TEMPERATURESARE NECESSARY TO OBTAIN ADEQUATE BOOSTER OUTPUT ADDANANTI SCALD VALVE FOR HOT WATER SUPPLIED TO FIXTURES INSERT A CAUTION IF BUILDING COLD WATER SUPPLY HAS A BACKFLOW PREVENTE...

Страница 21: ...OOSTER OUTPUT ADD AN ANTI SCALD VALVE FOR HOT WATER SUPPLIED TO FIXTURES PIPE RELIEF VALVE TO OPEN DRAIN WHEN USING A STATE T 140 200 350 OR 400 STORAGE TANK USE LOWER 3 4 OPENING FOR TANK TEMPERATURE...

Страница 22: ...ANIFOLD KIT PART NO 78694 DIMENSIONS A INCHES CM MODEL LOW PROFILE VERTICAL HOOD A SBD MODELS 120 69 75 177cm 154 73 00 185cm 180 67 50 171cm 197 75 00 192cm 198 75 00 192cm 199 67 50 171cm 200 72 00...

Страница 23: ...tallations contact State Water Heaters Technical Support Center at 1 800 527 1953 TABLE 5 MANIFOLD GAS PRESSURE IN INCHES OF WATER COLUMN ALL MODELS TYPE OF GAS NATURAL PROPANE 3 5 10 0 Gas pressure s...

Страница 24: ...PURGE DISCHARGE MUST NOT ENTER CONFINEDAREASORSPACESWHEREIGNITIONCANOCCUR THE AREA MUST BE WELL VENTILATED AND ALL SOURCES OF IGNITION MUST BE INACTIVATED OR REMOVED WARNING THE GAS VALVE MUST HAVE B...

Страница 25: ...25 FOR NATURAL GAS MODELS FOR YOUR SAFETY READ BEFORE OPERATING OPERATING INSTRUCTIONS FOR YOUR SAFETY READ BEFORE OPERATING...

Страница 26: ...26 FOR PROPANE GAS MODELS FOR YOUR SAFETY READ BEFORE OPERATING OPERATING INSTRUCTIONS TO TURN OFF GAS TO THE APPLIANCE...

Страница 27: ...the damper disc manually or motor damage will occur If the water heater does not operate with the Service Switch in either position Refer to the Troubleshooting Sections and Operational Checklist sec...

Страница 28: ...REVENTIVE MAINTENANCE CHECK THE PILOT At least once a year check the pilot burner fig 14 and the main burner fig 15 for proper operation Refer to the following pilot and main burner sections PILOT BUR...

Страница 29: ...a manometer to the gauge port and refer to Table 5 for correct manifold pressure 2 Use this formula to clock the meter Be sure that other gas consuming appliances are not operating during this interva...

Страница 30: ...heater and replacement of the factory installed magnesium anodes with aluminum anodes may correct the condition Occasionally water softener companies recommend removal of heater anodes for odor reason...

Страница 31: ...d screws securing tank cleanout plate and remove plate 4 Remove lime scale or sediment using care not to damage the glass lining 5 Inspect cleanout plate gasket if new gasket is required replace with...

Страница 32: ...ed by the UN LIME it can be reused if not the UN LIME should be replaced TROUBLESHOOTING IGNITION MODULE SYSTEM Before calling your service agent the following checklist should be examined to eliminat...

Страница 33: ...breaker 5 Disconnect switch off 6 Harness not plugged into appliance receptacle A FLUE DAMPER OPEN OR OPENING Unit is calling for heat and damper disc should be in vertical position VOLTAGE ACROSS 4...

Страница 34: ...slower Call serviceman Check gas input If incorrect adjust gas pressure or replace main burner orifice Draft hood not installed or Call serviceman Install draft hood or baffles as one or more flue ba...