14
DISCONNECT THE HEATER AND ITS MANUAL GAS SHUTOFF
VALVE FROM THE GAS SUPPLY PIPING SYSTEM DURING ANY
SUPPLY PRESSURE TESTING EXCEEDING 1/2 PSIG (3.45 Kpa).
GAS SUPPLY LINE MUST BE CAPPED WHEN DISCONNECTED
FROM THE HEATER FOR TEST PRESSURES OF 1/2 PSIG (3.45
Kpa) OR LESS. THE APPLIANCE NEED NOT BE DISCONNECTED,
BUT MUST BE ISOLATED FROM THE SUPPLY PRESSURE TEST
BY CLOSING THE MANUAL GAS SHUTOFF VALVE.
GAS METER SIZE — NATURAL GASES ONLY
Be sure the gas meter has sufficient capacity to supply the full
rated gas input of the water heater as well as the requirements of
all other gas fired equipment supplied by the meter. If gas meter
is too small, ask the gas company to install a larger meter having
adequate capacity.
GAS PRESSURE REGULATOR
The gas pressure regulator is built into the gas valve and is
equipped to operate on the gas specified on model and rating
plate. The regulator is factory adjusted to deliver gas to burner
at correct water column pressure allowing for a nominal pressure
drop through the controls.
The minimum gas supply pressure for input adjustment must not
be less than 4.5” W.C. (1.12 Kpa) for natural gas and 11.0” W.C.
(2.74 Kpa) for propane gas.
FIGURE 11
Do not subject the combination gas valve to inlet gas pressures of
more than 14.0” W.C. (3.48 Kpa) - natural gas, 14.0” W.C. (3.48
Kpa) - propane gas. A service regulator is necessary if higher gas
pressures are encountered.
Gas pressure specified in Table 5, refer to flow pressure taken at
pressure tap of automatic gas valve while heater is operating.
GROUNDING INSTRUCTIONS
This water heater must be connected to a grounded metal,
permanent wiring system; or an equipment grounding conductor
must be run with the circuit conductors and connected to the
equipment grounding terminal or lead on the water heater.
HEATER WIRING
All electrical work must be installed in accordance with the
latest version of the National Electrical Code ANSI/NFPA No. 70,
and must conform to all local code authority having jurisdiction.
AN
ELECTRICAL GROUND IS REQUIRED TO REDUCE RISK OF
ELECTRICAL SHOCK OR POSSIBLE ELECTROCUTION.
If any of the original wire as supplied with the appliance must be
replaced, use only type 105°C thermoplastic or equivalent. 250
0
C
type F must be used for the flame sensor leads and the spark
ignition cable must be high voltage 250°C.
Содержание SBD100199*
Страница 35: ...35...