ELECTRONIC IGNITION CONTROL

Each heater is equipped with a Honeywell ignition module. The 

solid state ignition control, fig. 4, ignites the pilot burner gas by 

creating a spark at the pilot assembly.  Pilot gas is ignited and 

burns during each running cycle.  The main burner and pilot gases 

are cut off during the OFF cycle.  Pilot gas ignition is proven by the 

pilot sensor.  Main burner ignition will not occur if the pilot sensor 

does not first sense pilot ignition.

HONEYWELL IGNITION MODULE

S8600M Continuous Re-Try

FIGURE 4

AUTOMATIC FLUE DAMPER DEVICE

All units are equipped with an automatic flue damper that reduces 

heat  loss  during  the  OFF  cycles.   The  automatic  flue  damper 

drive assembly is a field replaceable part and may be obtained 

by contacting State Water Heaters.

Each automatic flue damper drive assembly is equipped with a 

“Service Switch”, as shown in figure 5.

FIGURE 5

The “Service Switch” has 2 positions: AUTOMATIC OPERATION 

and HOLD OPEN DAMPER.  For normal operation the switch 

should be in the AUTOMATIC OPERATION position.

If there is a problem with the damper the “Service Switch” can be 

placed in the HOLD OPEN DAMPER position.  When the switch 

is placed in the HOLD OPEN DAMPER position the damper disc 

will rotate to the open position and the heater may be used until 

vent assembly is repaired or replaced.  DO NOT turn the damper 

disc manually; damage will occur to the drive assembly if operated 

manually.  Refer to TESTING DAMPER OPERATION section of 

this manual for additional information. 

                     

CIRCULATING PUMP

A  circulating  pump  is  used  when  a  system  requires  a 

circulating loop or there is a storage tank used in conjunction 

with the heater.  Refer to the piping diagrams in this manual 

for  electrical  hookup  information  and  install  in  accordance 

with the current edition of the National Electrical Code

 ANSI/

NFPA No. 70.

Only  all  bronze  circulators  should  be  used  with  commercial 

 

water heaters.

Although circulators are oiled and operated by the manufacturer 

some circulators must be oiled again before operating.  Please 

refer to manufacturer’s instructions.  

DISHWASHING MACHINE REQUIREMENT

These  appliances  meet  the  NSF  Standard  5  for  sanitary 

installations  when  used  with  the  following  leg  kits,  Part  No’s. 

6570-0 and 6570-7.

All  dishwashing  machines  meeting  the  National  Sanitation 

Foundation requirements are designed to operate with water 

flow  pressures  between  15  and  25  psi  (103  Kpa  and  173 

Kpa).    Flow  pressures  above  25  psi  (173  Kpa),  or  below 

15  psi  (103  Kpa),  will  result  in  improperly  sanitized  dishes.  

Where pressures are high, a water pressure reducing or flow 

regulating control valve should be used in 180°F (82°C) line to 

the dishwashing machine, and should be adjusted to deliver 

water between these limits.

The National Sanitation Foundation also recommends circulation 

of  180°F  (82°C)  water.    Where  this  is  done,  the  circulation 

should be very gentle so that it does not cause any unnecessary 

turbulence inside the water heater.  The circulation should be 

just enough to provide 180°F (82°C) water at the point of take-off 

to the dishwashing machine.  Adjust flow by means of the plug 

cock in the circulating line.

INSTALLATION INSTRUCTIONS

REQUIRED ABILITY

INSTALLATION  OR  SERVICE  OF  THIS  WATER  HEATER 

REQUIRES ABILITY EQUIVALENT TO THAT OF A LICENSED 

TRADESMAN  IN  THE  FIELD  INVOLVED.    PLUMBING, AIR 

SUPPLY, VENTING, GAS SUPPLY AND ELECTRICAL WORK 

 

ARE REQUIRED.

 WARNING

FAILURE TO FOLLOW THESE INSTRUCTIONS CAN RESULT 

IN SERIOUS PERSONAL INJURY OR DEATH.

UNCRATING

The heater is shipped with the flue damper already installed

.  The 

wiring conduit runs from the thermostat to the damper drive cover.  

Before turning unit on, check to make sure the wiring conduit is 

securely plugged into damper drive. 

LOCATING THE HEATER

When  installing  the  heater,  consideration  must  be  given  to 

proper  location.    Location  selected  should  be  as  close  to  the 

stack or chimney as practicable, with adequate air supply and as 

centralized with the piping system as possible.

Содержание SBD100199*

Страница 1: ...FERENCE CAUTION TEXT PRINTED OR OUTLINED IN RED CONTAINS INFORMATION RELATIVE TO YOUR SAFETY PLEASE READ THOROUGHLY BEFORE INSTALLING AND USING THIS APPLIANCE Thank you for buying this energy efficien...

Страница 2: ...FIGURE 1 ROUGH IN DIMENSIONS See Tables 1A and 1B SBD71120 models are approved for 5 13 cm venting using a 6 15 cm to 5 13 cm reducer...

Страница 3: ...5 NA 1 50 1 50 NA 1 50 1 50 750 Lbs 862 Lbs 89 kW Hr 246 L 191 cm 12 cm 167 cm 145 cm 51 cm NA 1 2 149 cm 20 cm 70 cm NA 1 50 1 50 NA 1 50 1 50 341 Kg 391 Kg SBD85365 365 000 BTR Hr 85 Gal 79 50 4 50...

Страница 4: ...89 kWh 365 000 107 kWh 399 000 117 kWh and 500 000 147 kWh Btuh with a recovery rating of 277 3 gph 1049 Lph or more also comply with ANSI Z21 10 3 as an automatic instantaneous type heater Detailed...

Страница 5: ...such as having a cold or diminishing sense of smell with age For these reasons the use of a propane gas detector is recommended IF YOU EXPERIENCE AN OUT OF GAS SITUATION DO NOT TRYTO RELIGHTAPPLIANCE...

Страница 6: ...cannon must be oriented correctly for proper function There is a marked range on the pipe nipple portion of the hydro cannon that must be aligned with the top of the inlet spud A label above the jacke...

Страница 7: ...d with commercial water heaters Although circulators are oiled and operated by the manufacturer some circulators must be oiled again before operating Please refer to manufacturer s instructions DISHWA...

Страница 8: ...t least 2 5cm deep with length and width at least 2 5cm greater than the diameter of the heater and must be piped to an adequate drain The pan must not restrict combustion air flow For appliance insta...

Страница 9: ...insulation caulking vapor barrier etc air for combustion ventilation and draft hood dilution must be obtained from outdoors The installation instructions for confined spaces in tightly constructed bui...

Страница 10: ...ere will be a minimum of turbulence inside the heater If a water heater is installed in a closed water system contact the water supplier or local plumbing inspector on how to control this situation WA...

Страница 11: ...0 197 198 199 200 Input 180 000 190 000 199 000 Btuh Total Vent Height Feet Draft Hood 6 6 8 10 15 20 30 50 100 Input Btuh Rise Vent Connector Diameter in inches 180 000 1 Ft 8 8 8 8 8 7 7 7 190 000 8...

Страница 12: ...10 10 8 8 8 Number of Combined Input Heaters in Thousands of Btuh Manifold Common Vent Diameter 2 610 14 14 12 12 12 10 10 10 3 915 16 16 16 14 14 12 12 12 4 1220 18 18 16 16 16 14 14 12 MODEL 365 40...

Страница 13: ...0 60 66 138 260 530 810 1520 2400 4300 8800 70 61 125 240 490 750 1400 2250 3900 8100 80 57 118 220 460 690 1300 2050 3700 7500 90 53 110 205 430 650 1220 1950 3450 7200 100 50 103 195 400 620 1150 18...

Страница 14: ...input adjustment must not be less than 4 5 W C 1 12 Kpa for natural gas and 11 0 W C 2 74 Kpa for propane gas FIGURE 11 Do not subject the combination gas valve to inlet gas pressures of more than 14...

Страница 15: ...Install in accordance with all local codes Use of the top inlet water connection requires installation of an inlet dip tube refer to figure 12 The tube is supplied in the heater Follow caution labels...

Страница 16: ...OULD NOT EXCEED SAFE USE TEMPERATUREATFIXTURES SEEWATERTEMPERATURECONTROL WARNING ON PAGE 27 IF HIGHER PREHEAT TEMPERATURES ARE NECESSARY TO OBTAIN ADEQUATE BOOSTER OUTPUT ADD AN ANTI SCALD VALVE FOR...

Страница 17: ...ED ON DURING THE RINSE OPERATION AND OPEN OFF WHEN DISHWASHER IS NOT OPERATING OR WHEN ON LONG STANDBY NOTE 2 INSTALL LINE TEMPERATURE CONTROL IN AN UNINSULATED TEE BEYOND THE DISHWASHING MACHINE TAKE...

Страница 18: ...nstallation diagrams on the following pages are typical TWO TEMPERATURE TWO HEATERS ONE PRE HEATER ONE BOOSTER HEATER WITH OR WITHOUT BUILDING RECIRCULATION The discharge opening of the temperature an...

Страница 19: ...TE 3 ADJUST PLUG COCK SO THE SANITIZING LOOP FLOW RATE DOES NOT CAUSE UNNECESSARY TURBULENCE IN THE TANK PIPE RELIEF VALVE TO OPEN DRAIN INSTALL IN ACCORDANCE WITH LOCAL CODES CIRCULATING RETURN LINE...

Страница 20: ...GHER PREHEAT TEMPERATURESARE NECESSARY TO OBTAIN ADEQUATE BOOSTER OUTPUT ADDANANTI SCALD VALVE FOR HOT WATER SUPPLIED TO FIXTURES INSERT A CAUTION IF BUILDING COLD WATER SUPPLY HAS A BACKFLOW PREVENTE...

Страница 21: ...OOSTER OUTPUT ADD AN ANTI SCALD VALVE FOR HOT WATER SUPPLIED TO FIXTURES PIPE RELIEF VALVE TO OPEN DRAIN WHEN USING A STATE T 140 200 350 OR 400 STORAGE TANK USE LOWER 3 4 OPENING FOR TANK TEMPERATURE...

Страница 22: ...ANIFOLD KIT PART NO 78694 DIMENSIONS A INCHES CM MODEL LOW PROFILE VERTICAL HOOD A SBD MODELS 120 69 75 177cm 154 73 00 185cm 180 67 50 171cm 197 75 00 192cm 198 75 00 192cm 199 67 50 171cm 200 72 00...

Страница 23: ...tallations contact State Water Heaters Technical Support Center at 1 800 527 1953 TABLE 5 MANIFOLD GAS PRESSURE IN INCHES OF WATER COLUMN ALL MODELS TYPE OF GAS NATURAL PROPANE 3 5 10 0 Gas pressure s...

Страница 24: ...PURGE DISCHARGE MUST NOT ENTER CONFINEDAREASORSPACESWHEREIGNITIONCANOCCUR THE AREA MUST BE WELL VENTILATED AND ALL SOURCES OF IGNITION MUST BE INACTIVATED OR REMOVED WARNING THE GAS VALVE MUST HAVE B...

Страница 25: ...25 FOR NATURAL GAS MODELS FOR YOUR SAFETY READ BEFORE OPERATING OPERATING INSTRUCTIONS FOR YOUR SAFETY READ BEFORE OPERATING...

Страница 26: ...26 FOR PROPANE GAS MODELS FOR YOUR SAFETY READ BEFORE OPERATING OPERATING INSTRUCTIONS TO TURN OFF GAS TO THE APPLIANCE...

Страница 27: ...the damper disc manually or motor damage will occur If the water heater does not operate with the Service Switch in either position Refer to the Troubleshooting Sections and Operational Checklist sec...

Страница 28: ...REVENTIVE MAINTENANCE CHECK THE PILOT At least once a year check the pilot burner fig 14 and the main burner fig 15 for proper operation Refer to the following pilot and main burner sections PILOT BUR...

Страница 29: ...a manometer to the gauge port and refer to Table 5 for correct manifold pressure 2 Use this formula to clock the meter Be sure that other gas consuming appliances are not operating during this interva...

Страница 30: ...heater and replacement of the factory installed magnesium anodes with aluminum anodes may correct the condition Occasionally water softener companies recommend removal of heater anodes for odor reason...

Страница 31: ...d screws securing tank cleanout plate and remove plate 4 Remove lime scale or sediment using care not to damage the glass lining 5 Inspect cleanout plate gasket if new gasket is required replace with...

Страница 32: ...ed by the UN LIME it can be reused if not the UN LIME should be replaced TROUBLESHOOTING IGNITION MODULE SYSTEM Before calling your service agent the following checklist should be examined to eliminat...

Страница 33: ...breaker 5 Disconnect switch off 6 Harness not plugged into appliance receptacle A FLUE DAMPER OPEN OR OPENING Unit is calling for heat and damper disc should be in vertical position VOLTAGE ACROSS 4...

Страница 34: ...slower Call serviceman Check gas input If incorrect adjust gas pressure or replace main burner orifice Draft hood not installed or Call serviceman Install draft hood or baffles as one or more flue ba...

Страница 35: ...35...

Страница 36: ...36 500 Tennessee Waltz Parkway Ashland City TN 37015 Phone 800 365 0024 Fax 800 644 9306 www statewaterheaters com...

Отзывы: