Header can be retrieved by Refcon, Logman, StarView and can be viewed in Refcon, LogView and
StarView.
Extended Log Type 1 can only be retrieved by Logman and StarView and shown in LogView and
StarView.
Extended Log Type 2 can only be retrieved by StarView and viewed in StarView.
StarView is the unique program designed for communication with a Star cool unit through a serial
connection to a PC.
Alarm Action System (AAS)
This function defines what to do if a sensor is defect. The strategy is to substitute the missing
sensors reading with the value from another a constant so that the unit can maintain its
functionality with reduced precision.
Temperature control
Chill mode
Defect sensor(s)
Substitution sensor / Action Alarm
Tsup1 (2)
Tact = Tsup2 (1)
Tsup1 and Tsup2
Tact = Tret + constant
611, Too many sensor err
Tsup1, Tsup2 and Tret
Tact = Tevap + constant
Tsup1, Tsup2, Tret and Tevap
**
600, No control sensor
Freeze mode
Defective sensor(s)
Substitution sensor / Action Alarm
Tret
Tact = Tevap + constant
Tret and Tevap
Tact = Tsup1 + constant
611, Too many sensor err
Tret, Tevap and Tsup1
Tact = Tsup2 + constant
Tret, Tevap, Tsup1 and Tsup2
**
600, No control sensor
** = No more available sensors for substitution.
Expansion valve control
Defective sensor(s)
Substitution sensor / Action Alarm
Psuc
Emergency injection
611, Too many sensor err
Tsuc
Emergency injection
611, Too many sensor err
Condenser fan control
Defective sensor(s)
Substitution sensor / Action Alarm