AirEx sens sup LO
Warning
Description
Controller Internal Voltage Reference Fault
Cause
Indication of controller internal voltage reference fault
Trouble
shooting
Possible causes:
•
Defect power supply for controller PCB.
•
Defect sensor pulling power supply down.
•
Defect controller PCB.
Accompanied alarms:
•
There may be sensor alarms, AL 3XX.
•
AL 801 will be activated during FT- or PTI test.
Trouble shooting:
1) Check if there are other active (sensor) alarms. Clear these alarms first
using their trouble shooting.
2) Access the “special menu” by pressing
for more than 3 sec. Scroll down
until you see the label “U AirEx” in the display. The value of “U AirEx“ should
be in the range between 4.80 V DC and 5.05 V DC.
3) While displaying “U AirEx“, remove the connector at AirEx potentiometer.
−
If “U AirEx“ is now inside the correct above range (4.80 – 5.05 V DC),
the AirEx potentiometer is defective. Replace the AirEx potentiometer
−
If “U AirEx” is still outside the above range, proceed to next step.
4) While displaying “U AirEx“, disconnect “AirEx” from the terminals according
to wiring schematics inside in the control cabinet.
−
If “U AirEx” is now inside the above range the cable for “AirEx” is defect.
Mount connector correctly or replace connector cable for “AirEx”.
−
If “U AirEx” is still outside, correct the above range. The controller PCB is
defect. Replace the controller door.
Criteria
Reference voltage AirEx below 4.80 V DC
Controller
action
None
Log
X
Alarm
Alarm light
Off
Consequence
Elimination
Log data
Parm 1
Parm 2
Parm 3
Parm 4
Parm 5
Active/Inactive Low limit High limit
Actual value A/D channel
The measured temperature is internal on the controller PCB and cannot be measured