129 of 222 pages
Operating and service manual
525
FC overload
Warning
Description
FC Overload Warning
Cause
Indication of problems with compressor
Trouble
shooting
(W9)
Possible causes:
•
The FC cannot supply enough power to the compressor.
•
Insufficient cooling for the FC.
•
Defect FC.
Accompanied alarms:
•
AL 522 or AL 525 may also be active and should be checked first.
Trouble shooting:
At very high ambient temperatures and very low setpoint temperatures, the FC
may get too hot to generate enough power. It can therefore be cooled by the
refrigerant in the compressor.
1.
Check that all bolts fixing the FC to the compressor are fastened and nothing
is jammed between the FC and the compressor.
2. The power cable for the compressor motor (Mcpr) may have been mounted
incorrectly and therefore the cooling contact between the FC and the
compressor is not good enough. Check the motor cable and replace it if it is
defect. Fasten bolts properly for better cooling.
3. The compressor is wearing down and drawing increasingly power from the
FC. Check other alarms if there have been more alarms from the FC.
a. If the ambient temperature is not high, the compressor must be replaced.
b. If the ambient temperature is high, the compressor and FC should be ok
but close to operating limit. Monitor unit and see if problem continues.
4. The FC is defective and must be replaced.
If no FC replacement is available, the unit can be rewired for emergency
operation: See “Emergency Operation” p. 50
Criteria
FC load has exceeded warning limit of 24 Amp
Controller
action
None
Log
X
Alarm
X
Alarm light
Off
Consequence
If not solved, this problem can cause FC to stop due to AL 513
Elimination
Warning will be marked as inactive in alarm list when reset by FC. Alarm may then be
deleted.
Log data
Parm 1
Parm 2
Parm 3
Parm 4
Parm 5
Active/Inactive Freq FC
I FC
Psuc
Pdis