Delayed Egress System, Model DE-MC521 

Installation Instructions 

Quick-Reference Guide 

204038 

Rev. B 4/12/08

 

 

 

 

Prohibition on Copying 

Any unauthorized reproduction, disclosure or distribution of copies by any person of any 
portion of this work may be a violation of copyright law of the United States of America 
and other countries, could result in the awarding of statutory damages of up to $250,000 
(17 USC 504) for infringement, and may result in further civil and criminal penalties. All 
rights reserved. 

 

Stanley Access Technologies                     

Quick-Reference Guide   

                              

 

 

Содержание DE-MC521

Страница 1: ... distribution of copies by any person of any portion of this work may be a violation of copyright law of the United States of America and other countries could result in the awarding of statutory damages of up to 250 000 17 USC 504 for infringement and may result in further civil and criminal penalties All rights reserved Stanley Access Technologies Quick Reference Guide ...

Страница 2: ...ing the Components on the Header Cover or Jamb 5 3 4 Installing the 4 Contact Plate Assembly P N 516908 for Biparting Doors 6 3 5 Installing the 4 Contact Plate Assembly P N 516908 for Single Slide Doors 7 3 6 Installing the Label P N 516905 8 3 7 Wiring the Delayed Egress Assembly 9 3 8 Operational Checkout of the Delayed Egress System 9 3 9 Troubleshooting the Delayed Egress System 10 3 10 Repla...

Страница 3: ...idual who pushes the panic bar is denied egress for 15 or 30 seconds 1 2 Applicability This manual is ONLY applicable to the Stanley Dura Glide DE MC521 Delayed Egress system Standard MC521 slide installation manual is a pre requisite for this installation manual Instructions for installing Transom installation optional accessories such as access control locks access control consoles key switches ...

Страница 4: ...red for Installation 2 1 1 UL listed 24 VDC power supply 2 1 2 Fail secure solenoid lock 2 1 3 Small screwdriver 2 1 4 Severence tool P N CK 3 4 45 for adding nuts to the nut track 2 1 5 Rotary Key Switch Instruction Manual Stanley Access Technologies Document No 203926 2 1 6 Power key switch assembly P N 415119 ...

Страница 5: ...t Block Assembly Stanley Access Technologies 516907 Recessed Panic Pushbar with Switch Adams Rite 185060 Detent Block for Delayed Egress Stanley Access Technologies 516906 Shear Magnet Locks GEM 714082 3 1 1 Refer to Figure 1 and with the red wire at the top of the assembly POSITION the 4 contact block assembly at the lead edge of the hanger 3 1 2 Using two 8 32 pan head screws and 8 external toot...

Страница 6: ...21 Controller Replace the existing MC521 with DE MC521 P N 516928 Terminal block assembly Buzzer and bracket assembly 3 2 2 SECURE all wire harnesses with cable ties 3 3 Installing the Components on the Header Cover or Jamb 3 3 1 INSTALL power key switch assembly as follows If installation is a Dura Glide 3000 Refer to 203926 Rotary Key Switch Instruction Manual for machining template and MOUNT po...

Страница 7: ...doors and ENSURE that the doors close at the center of the header b MARK the center of the header onto the back of the header c POSITION the 4 contact plate onto the header and MARK the location of the mounting holes CAUTION The two top mounting holes for the 4 contact plate assembly are located above the track tube When drilling these two holes use caution to ensure that the drill bit does not ni...

Страница 8: ...embly for left side or right side mounting as follows If left side mounting refer to Figure 4 UNSCREW the green wire from the back of the plate and ASSEMBLE it above the white wire If right side mounting refer to Figure 4 UNSCREW the WHITE wire from the back of the plate and ASSEMBLE it above the green wire 3 5 2 Refer to Figure 5 and INSTALL the 4 contact plate assembly as follows a CLOSE the DOO...

Страница 9: ...block assembly on the hanger to ensure the electrical connection to the door panel The position of the four contact switch block assembly can be adjusted for vertical alignment 3 5 3 CYCLE the door several times and ENSURE the 4 contact switch block assembly on the hanger leading edge mates properly with the center contact plate as the door closes 3 6 Installing the Label P N 516905 3 6 1 INSTALL ...

Страница 10: ...ss System 3 8 1 Refer to 204003 MC521 Installation and Operation Manual Perform FIS Then SET the door for delayed egress as follows NOTE The door can be set for delayed egress using either the pushbuttons or the Palm The following steps describe setting delayed egress using the pushbuttons INDEX 18 Value 00 is OFF not evaluated by UL INDEX 18 Value 01 is 15 sec INDEX 18 Value 02 is 30 sec 3 8 2 CY...

Страница 11: ...K2 LED is OFF Table 3 3 Symptoms and Remedy Symptom Remedy Door set for CLOSED LOCKED and door gets to closed position Delayed egress starts without pressing push bar The dE indication is displayed on MC521 The buzzer turns ON K2 LED is OFF K1 LED is ON And shear locks de energize after 15 30 seconds Check connections from push bar switches to two contact transfer contacts to quad transfer contact...

Страница 12: ...alarm input open or missing The 24 VDC power supply disconnected TB2 10 2 24 VDC The bridge on terminal block 2 3 is loose Check 24 VDC power supply TB2 10 3 24 VDC The 24 VDC power supply is disconnected TB2 10 4 24 VDC MC521 is selected for Fail Safe Door position switch is not closed TB1 7 TB2 10 5 24 VDC The bridge on terminal block 0 1 or 2 3 is loose Fire alarm input open or missing The 24 V...

Страница 13: ... Switch Assembly 415119 Stanley Access Technologies 4 Contact Block Assembly 516907 Stanley Access Technologies 4 Contact Plate Assembly 516908 Stanley Access Technologies 2 Contact Block Assembly 516909 Stanley Access Technologies 2 Contact Plate Assembly 516910 Stanley Access Technologies Shear Magnet Locks 714082 GEM Reset Switch 413584 Stanley Access Technologies Push Bar Cartridge with Switch...

Страница 14: ...L TRANSFER CONTACT SHEAR LOCK TB1 10 0 VDC TB1 9 TB1 5 BUZZER CONTROL SHEAR LOCK CONTROL DUMMY PUSH BAR RELAY FIRE ALARM INPUT OR JUMPER TERMINAL BLOCK TB5 4 COMMON TB5 10 SHEAR LOCK CONTROL DE MC521 CONTROL BOX P N 516928 TB1 1 15 VDC QUAD TRANSFER CONTACTS BRIDGE TB2 10 TB2 9 OPTIONAL RESET SWITCH BRIDGE 1 2 3 4 5 6 7 8 9 10 11 A1 A2 22 21 14 11 A1 A2 NC C NO C TB1 8 SOLENOID LOCK CONTROL OR RD ...

Страница 15: ...2 3 4 5 6 7 8 9 10 RD BK BUZZER 21 11 24 14 A2 A1 RELAY K1 22 12 NO COM NC COIL 21 11 24 14 A2 A1 RELAY K2 22 12 NO COM NC COIL 10 9 8 7 6 5 4 3 2 1 LED LED BK OR RD WH GN BK RD BK BK RD RD BK SHEAR LOCK P N714082 PUSH BAR CARTRIDGE W SWITCH P N 185061 2 CONTACT PLATE ASSEMBLY P N 516910 4 CONTACT BLOCK ASSEMBLY P N 516907 TERMINAL BLOCK AND RELAY ASSEMBLY P N 516913 P N 415109 GROUND SHIELD RESET...

Страница 16: ...agram P N 185071 Sheet 2 of 4 FIELD TERMINAL BLOCK WIRING DE001_2 TO DE MC521 TO 4 CONTACT PLATE ASSEMBLY P N 516908 EXISTING WIRING PART OF TB ASSY 21 11 24 14 A2 A1 RELAY K1 22 12 NO COM NC COIL 21 11 24 14 A2 A1 RELAY K2 22 12 NO COM NC COIL 10 9 8 7 6 5 4 3 2 1 LED LED RD WH GN BK GROUND SHIELD RD OR BK GN BL WH ...

Страница 17: ...agram P N 185071 Sheet 3 of 4 DE001_3A FIELD DE MC521 CONTROLLER WIRING TO TB 516913 TO BUZZER AND BRACKET ASSEMBLY P N 415109 TB1 TB2 TB3 TB4 TB5 TB2 1 2 3 4 5 6 7 8 9 10 24 VDC POWER SUPPLY TB5 1 2 3 4 5 6 7 8 9 10 RD WH GN BL TB1 1 2 3 4 5 6 7 8 9 10 RD BK BK OR GROUND SHIELD RESET SWITCH OPTIONAL SHIELDED GROUND ...

Страница 18: ...001_4 FIELD POWER SWITCH WIRING DE MC521 CONTROLLER P N 516928 TB1 TB2 TB3 TB4 TB5 WH WH GN RD BK RD WH 8 7 2 ON OFF SCHEMATIC FOR THE SWITCH REAR VIEW COM PIN 2 PIN 8 BK WH GN HARNESS 412544 OR 412545 BK GN WH 3 2 1 3 2 1 LINE NEUTRAL EARTH GROUND GROUND SCREW IN HEADER 120 VAC LINE HARNESS 415117 POWER OFF POWER ON POWER SWITCH P N 415119 BK RD ...