All these error messages cause the ST535C to terminate the firing. The alarm buzzer
will sound once per second. To reset the ST535C turn off the power to the instrument
and have the fault investigated and rectified by your installer or kiln service engineer.
Technical note: these error messages will cause the alarm relay
to open.
Note: these error messages are provided to detect kiln faults
and so offer some protection to the kiln.
Program Error. This error message is displayed if
a potential error is detected within the firing pro-
gram when the ► key is pressed to start a firing.
The alarm buzzer will sound 3 times and the seg-
ment display will show the suspect segment number. To clear this error press the ►
key. The ST535C will now enter programming mode to allow the suspect program to be
viewed and altered if necessary. If a fault is found then correct it. If no fault is found
then press the ► key again to force the firing program to start. A potential program-
ming error is defined as a very low ramp rate to a very low temperature. Such a pro-
gramming fault might cause very long firing times with potential kiln damage.
Firing Program Errors
Internal data conversion circuit (ADC) error.
Maximum allowable differential temperature
between zones exceeded. The temperature of
zone 2 or zone 3 has varied from zone 1 by an
installer selectable limit.
ERROR:8
ERROR:9
ERROR:P