2.6 Single UPS Installation 

Installation and wiring must be set in accordance with the national and local codes. 
 

2.6.1 UPS Input/Output Wiring 

1.  Ensure the input feed wire and breakers are rated for the current capacity of the UPS to avoid the 

hazards of electric shock or fire. Se

5.2 Nominal UPS Output Current

 for maximum current. 

 

2.  Remove the terminal block cover on the rear panel of UPS. Then, connect the input and output 

wires according to 

Figure 8

.  

 

NOTE:

  Connect the earth ground wire first when making wire connection. Disconnect the earth 

ground wire last when making wire disconnection. 

 

 

 

 

 

NOTE 1: 

Make sure that the wires are connected tightly with the terminals.  

NOTE  2: 

Install the output breaker between the output terminal and the load. The breaker should be 

qualified with leakage current protection if necessary. 

 

Figure 8: 

Terminal block wiring diagram of UPS 

 

 

 

Input Ground 

Input Line 2 (N) 

Input Line 1 (L) 

Output Line 2 (N) 

Output Line 1 (L) 

Output Ground 

Содержание Unistar VP

Страница 1: ...003 2520 REV G UNISTAR VP 120 230V 50 60Hz 6 and 10kVA USER MANUAL...

Страница 2: ...oducts Company The Staco Energy Products Company reserves the right to modify the product described herein in order to improve it at any time and without notice 301 Gaddis Boulevard Dayton Ohio 45403...

Страница 3: ...t should be installed where it will not readily be subjected to tampering by unauthorized personnel f The use of accessory equipment not recommended by the manufacturer may cause an unsafe condition g...

Страница 4: ...tions Keep unauthorized personnel away from batteries There is a risk of explosion if batteries are replaced by an incorrect type Replace with same type and rating only Proper disposal of batteries is...

Страница 5: ...he Personal Protective Equipment PPE described below Personnel involved in the installation or maintenance of the unit must be properly clothed The following signs show the protective equipment that s...

Страница 6: ...S Installation 9 2 6 1 UPS Input Output Wiring 9 2 6 2 Battery Pack Installation 10 2 7 ISO Pack Installation 11 2 7 1 ISO Pack Input 11 2 7 2 ISO Pack Output 12 2 7 3 120V 120V Output 12 2 7 4 208V O...

Страница 7: ...y Pack Rear Panel 5 Figure 4 ISO Pack Rear Panel 5 Figure 5 3U Tower Installation 7 Figure 6 6U Tower Installation 7 Figure 7 Rack Mount Installation 8 Figure 8 Terminal block wiring diagram of UPS 9...

Страница 8: ...ectiveness is not recommended Do not use this equipment in the presence of a flammable anesthetic mixture with air oxygen or nitrous oxide The UPS is connected to a DC energy source battery The output...

Страница 9: ...attery is inadvertently grounded If inadvertently grounded remove source from ground Contact with any part of a grounded battery can result in electrical shock The batteries are recyclable The batteri...

Страница 10: ...he shipping package contains 1 UPS 1 user manual 1 monitoring software CD 1 RS 232 cable option 1 USB cable 1 battery cable Tower type installation supporters Rack type installation ears Battery cable...

Страница 11: ...control in parallel operation P modules only 5 Parallel port UPS communication in parallel operation P modules only 6 Intelligent slot Optional accessories to remotely control and monitor your UPS sy...

Страница 12: ...ery Pack Rear Panel 1 External Battery Connector 2 Battery pack output circuit breaker 2 3 ISO Pack Cabinet Rear Panel View Figure 4 ISO Pack Rear Panel 1 Input ground 2 Input terminals 3 Output termi...

Страница 13: ...em Single Line Diagram 2 4 1 UPS Single Line Diagram 2 4 2 ISO Pack Single Line diagram 240V X1 N X3 N L1 L2 X2 Output 208V N 240V 208V 120V 120V Note 1 Note1 Field installed jumper required for 208V...

Страница 14: ...n same method 2 For the UPS and matching Battery Pack a Assemble the two feet and two long extensions together to make one support with 10 25in 26cm width The other support can be copied in same metho...

Страница 15: ...the ears should face forward 2 Lift the UPS module and slide it onto the mounting shelves 3 Attach the UPS module to the rack by passing the screws nuts and washers user provided through mounting ears...

Страница 16: ...rear panel of UPS Then connect the input and output wires according to Figure 8 NOTE Connect the earth ground wire first when making wire connection Disconnect the earth ground wire last when making...

Страница 17: ...used For standard matching battery pack there is one DC breaker to disconnect the battery pack and the UPS But for other external battery packs contact your Staco Representative For the 10KVA model i...

Страница 18: ...of the UPS will be connected to the input terminals of the ISO Pack 240V X1 N X3 N L1 L2 X2 Input 208V N Figure 10 ISO Pack Input 1 line 240V System Figure 11 Wiring UPS output to ISO Pack 240V 208V...

Страница 19: ...re are 2 sets of 120V Each set can carry of the total UPS capacity Connect one load to X1 N and the other load to X3 N 120V 120V X1 N X3 N L1 L2 X2 Output N 120V 120V Figure 13 Output wiring of ISO Pa...

Страница 20: ...ut Jumper must be added between N and X3 as shown in Figure 15 Connect the load to X1 N Note 1 240V X1 N X3 N L1 L2 X2 Output N 240V Note 1 Note 1 Full rated jumper must be installed Figure 15 Output...

Страница 21: ...ernal Panel Furnished by Others 120V X1 N X3 N L1 L2 X2 Output N 208V 120V Note 1 Note 1 Full rated jumper must be installed Figure 16 Output wiring of ISO Pack 208V 120V 2 7 8 120V and 240V Output 12...

Страница 22: ...PO function open the terminals Figure 18 EPO connections on UPS WARNING The EPO RS 232 and USB circuits are an IEC 60950 safety extra low voltage SELV circuit This circuit must be separated from any h...

Страница 23: ...forbidden h frequency auto detect enable or disable i inverter short clear enable or disable 3 Turn on each UPS into the line mode or battery mode respectively see 3 5 1 Turn on the UPS with utility...

Страница 24: ...Page 17 2 9 2 Parallel Operation 1 Wire UPS parallel cables and Power cables as shown in below pictures Figure 20 Wiring of two UPS s in parallel Figure 21 Wiring of three UPS s in parallel...

Страница 25: ...to turn on the power supply UPS will enter power on mode After initialization UPS will enter No Output mode c Within 15 seconds press ON button again to turn on UPS d A few seconds later after UPS is...

Страница 26: ...de When input voltage is within acceptable range and bypass is enabled and the UPS inverter is not turned on or the inverter can t take the load the UPS will supply power to the load through bypass Ba...

Страница 27: ...supply power to the load NOTE When UPS is in Bypass mode the load is not protected by UPS 3 Press the ON ENTER button while LCD is on default home screen LCD will show a prompt page of Turn On 4 Move...

Страница 28: ...r to the section of changing battery quantity is consistent with actual connection 3 5 5 Battery Mode operation 1 When the UPS is in Battery mode the buzzer will beep according to different battery ca...

Страница 29: ...till be working if bypass status has been set to enable the output voltage of the UPS will still exist 3 To fully cut off the output please switch off the external input breaker A few seconds later th...

Страница 30: ...Page 23 3 6 LCD Operation...

Страница 31: ...nt Information Setting Alarm for selection 2 Press UP or DOWN button to select item 3 Press ON ENTER button to confirm the selection 4 Press OFF ESC button to exit to home page 3 6 2 2 Control items N...

Страница 32: ...e OFF ESC button in home page it is not necessary to enter into this control menu 2 Battery Test This item can be shown in all modes However battery test will not work in Battery Fault Eco mode 3 Mute...

Страница 33: ...to startup the UPS this instruction must be executed NOTE Before executing this instruction you must check if the system cables and connections are in correct and safe condition Please read the relate...

Страница 34: ...3 6 2 5 Setting Menu This menu is used to adjust the parameters or do calibration NOTE Not all settings will be available in every operation mode If the setting is not available in present mode the L...

Страница 35: ...s V default 264V Set the acceptable high voltage for bypass Setting range is from Rated Output Volt 11V to 276V 3 LowLoss V default 110V Set the acceptable low voltage for bypass Setting range is from...

Страница 36: ...cy could be from 46Hz to 64Hz Disable The output frequency will synchronize with the input frequency within 46 54 Hz for 50Hz system or within 56 64 Hz for 60Hz system NOTE CVCF means Constant Voltage...

Страница 37: ...justment should be suitable to battery specifications Other settings available in all operation modes Interface Description Other Setting Hot Standby Backup Time Hot Standby Status Disable Backup Time...

Страница 38: ...ED illuminates and the buzzer beeps continuously it means that there is a fatal error Users can get the fault code from the LCD panel Please refer to the trouble shooting table to check what problems...

Страница 39: ...lation is blocked by the wall or other goods 4 Load is too heavy 1 Make sure the ambient temperature is not over 40 C 2 Make sure the fan is OK 3 Make sure the ventilation is OK 4 Remove some loads if...

Страница 40: ...negative It means there is energy feedback into the internal of UPS from output It may be caused by regenerative load or caused by the current control failure in the parallel system Contact the facto...

Страница 41: ...me 7 hours recover to 90 capacity 9 hours recover to 90 capacity Float Charging Voltage 273 VDC Charge Current max 4 Amps PHYSICAL UPS Dimension in 17 24 x 5 15 x 23 85 WxHxD 17 24 x 5 15 x 27 00 WxHx...

Страница 42: ...nforced insulation or double insulated wire 5 4 Agency Listings Safety Safety Conformance IEC EN 62040 1 UL1778 4th Edition Safety Markings UL CE EMI Conducted Emission IEC EN 62040 2 FCC Part 15 Clas...

Отзывы: