Page | 14
2.7.6 Multiple Voltage Output
Due to limited terminal space, some connections for multiple output voltages need to be made external to
the ISO Pack.
2.7.7 120V and 208V Output
120V load connects to X3-N
208V load connects to X2-N (ref.
208V
External Panel
Furnished by Others
120V
X1
N
X3
N
L1
L2
X2
Output
N
208V
120V
Not
e 1
Note 1: Full rated jumper must be installed
Figure 16:
Output wiring of ISO Pack – 208V & 120V
2.7.8 120V and 240V Output
120V load connects to X3-N or X1-N
240V load connects to X1-N (ref.
240V
External Panel
Furnished by Others
120V
X1
N
X3
N
L1
L2
X2
Output
N
240V
120V
Not
e 1
Note 1: Full rated jumper must be installed
120V
Figure 17:
Output wiring of ISO Pack – 240V & 120V