Form No. 003-2282 Rev G
42
INTERNAL BATTERY
Battery Run Time @ Full Load
8
7
5
Type
Sealed Lead Acid
Maintenance Free, 20 each
12V/7AH,
240Vdc
Sealed Lead Acid
Maintenance Free, 20
each 12V/9AH,
240Vdc
Sealed Lead Acid
Maintenance Free, 20
each 12V/9AH,
240Vdc
Hot
– Swap Batteries
Yes
Recharge Time
4 hours to 90%
5 hours to 80%
*Extended Run Time
Battery Cabinets
SC-BP6000T-2, SC-BP6000T-3, SC-BP1100T-2, SC-BP1100T-3
(Refer To Run Time Chart)
COMMUNICATION Cards and Shutdown Software
(Optional)
SC-SNMP1
SNMP/WEB Network Card and Shutdown Software
SC-Contact/EPO
Dry Contact & EPO Card
SC-PK*
Parallel Cable kit contains two RJ45 cables and miscellaneous hardware for paralleling
Note: (2) slots available; both cards can be used simultaneously; RS232 Port is disabled when communication cards
are installed.
*- Required when using multiple UPS modules in a parallel configuration
EXTERNAL EXTENDED BATTERY CABINETS
(Optional)
Model
SC-BP6000T-2 & -3
SC-BP1100T-2 & -3
Type
Sealed Lead Acid
Maintenance Free,
-2: 40 each & -3: 60 each
12V/9AH, 240Vdc
Sealed Lead Acid Maintenance Free,
-2: 40 each & -3: 60 each
12V/9AH, 240Vdc
Hot
– Swap Cabinets
Yes
Battery Connection
Connector
Dimensions (H x W x D)
29.5” x 11.4” x 25.4”
Weight (lbs.)
326
EXTERNAL BATTERY CABINET CHARGER
(Optional)
SC-CHG-1000
1000W External Mount Battery Charger (1)
charger per every (2) External Battery Packs
Required
6.6”W x 11.1”D x 3.4”H
7 lbs.
Note: (1) External Battery Charger (P/N SC-CHG-1000) required for every (2) Extended Battery Cabinets
*PARALLEL DISTRIBUTION/BYPASS MODULE
(4 Units maximum)
SC-PKIT-2
Bypass Two (2)-6kVA units or One (1)-(8 or
10kVA) unit 60 Amp
10.5”W x 9.5”D x 3.7”H
11 lbs.
SC-PKIT-4
Bypass Four (4)-6kVA units or Two (2)-(8 or
10kVA) unit 120 Amp
10.5”W x 16.4”D x 3.7”H
20 lbs.
SC-PKIT-4200
Bypass Four (4)-(8 or 10kVA) units 200A
10.5”W x 16.4”D x 3.7”H
23 lbs.
*Parallel for capacity configurations can use (1) battery system sized for the ultimate capacity.
* Parallel for redundancy configurations require (1) battery system for each UPS.