Form No. 003-2282 Rev G
22
Start-up in Battery Mode (Cold Start)
3.5.1.10. Make sure the UPS has a fully charged battery pack. At least 1 set
(20pcs) of 12V/7AH batteries is required.
3.5.1.11. Push the UPS On Switch
once for approx. 5 seconds to initialize
the UPS. The alarm sounds twice. The LCD display will change from
drawing A1 to drawing G, and stay on for approx. 15 seconds.
3.5.1.12. Within 15 seconds, press the UPS On Switch
again for about 3
seconds, until the LCD display changes from drawing G to drawing H,
then the UPS will be in self-test Mode. The UPS will start the inverter to
energize the output in approx. one minute, and the LCD display will
show as drawing I. Failure to press the UPS On Switch within 15
seconds, will cause a failure to start and you will then have to repeat
steps 3.5.1.10 to 3.5.1.12 once again.
3.5.1.13.
G
Display shows
“Off”, which means the UPS pre-start is successful.
H
* Display shows Utility input is
“0” and Utility Abnormal.
I