1.1.23 The UPS offers CVCF (Constant Voltage Constant Frequency) setting
function.
a. For correct setting and wiring, please contact your local agent.
b. Do not attempt to configure the UPS for CVCF by yourself;
otherwise your warranty will be void.
1.1.24 This UPS has been designed and constructed to protect your assets
from the wide range of power aberrations experienced on Utility power lines
today. It is your insurance for reliable, clean and stable voltage supply. It is
worth taking care to install the system correctly and to have it maintained
correctly by your local dealer.
1.1.25 SAVE THESE INSTRUCTIONS - This Manual Contains Important
Instructions that should be Followed during Installation and Maintenance of
the UPS and Batteries.
1.1.26 Intended for Installation in a Controlled Environment.
1.1.27 CAUTION
– 6Kva - A load disconnect switch shall be provided by
others for the AC output circuit. To reduce the risk of fire, connect only to a
circuit provided with branch circuit over-current protection for 30 amperes
rating in accordance with the National Electric Code, ANSI/NFPA 70.
1.1.28 CAUTION
– 8/10Kva - To reduce the risk of fire, connect only to a
circuit provided with branch circuit over-current protection for 40 amperes
rating in accordance with the National Electric Code, ANSI/NFPA 70.
1.1.29 Use No. 10 AWG, 60
C copper wire and 22.1 lb-in Torque force when
connecting to terminal block.
1.2.
Storage Instruction
For extended storage through moderate climate, the batteries should be
charged for 12 hours every 3 months by connecting the UPS input to an
appropriate power source and start the UPS according to the instructions in
this manual. Repeat this procedure every 2 months under high temperature
environment.