Operating modes
Menu “4. Operating modes” is used to spe
-
cify the operating modes for the heating
circuit.
After an interruption of the mains voltage
the controller automatically returns to the
last operating mode selected!
The menu is closed by pressing “esc” or
selecting “Exit operating modes”.
Auto
= Automatic/Normal mode using the set times.
Continous Day
= The set values for day mode are used.
Continous Night
= The set values for night mode are used.
Reference Value
= Fixed flow temperature regardless of the outdoor temperature. The
desired flow temperature has to be set in menu 4.3.
14 day reference value
= Specific fixed flow temperatures can be set for the next 14
days in menu 4.4. After 14 days, the reference temperature of the 14th day is used until
the operating mode is changed.
Off
= Heating circuit is switched off (except Frost protection)
Settings range: Auto, Continous day, Continous night, Reference value, 14 day refer-
ence, Off
Default: Automatic
Auto
= Automatic/Normal mode using the set times.
Continous Day
= The set values for day mode are used.
Continous Night
= The set values for night mode are used.
Reference Value
= Fixed flow temperature regardless of the outdoor temperature. The
desired flow temperature has to be set in menu 4.6.
14 day reference value
= Specific fixed flow temperatures can be set for the next 14
days in menu 4.7. After 14 days, the reference temperature of the 14th day is used until
the operating mode is changed.
Off
= Heating circuit is switched off (except Frost protection)
Settings range: Auto, Continous day, Continous night, Reference value, 14 day refer-
ence, Off
Default: Automatic
4.1 Heat circuit
4.2 Heat circuit 2
Operating modes
The controller works with the set operating times and the corresponding
different reference flow temperature values only in the automatic mode.
Caution