49
Instruction for use | Supercal 5
11. Technical Information
11.1 Calculator Supercal 5
Temperature Measurement
Pt500 according to EN 60751
2- or 4-wire
Absolute temperature range
Approved range
Homologation range
Response limit
Temperature resolution t
Temperature resolution Δt
Environment class A
−20
°C to 200 °C
1 °C to 200 °C
3 K to 150 K
0,2 K
0,1 K
0.01 K
E1/M1
Temperature Measuring Cycle
Battery operated
Mains operated
10 s
3 s
Medium Temperature
Operation
Storage and transport
5 °C to 55 °C
−20 °C to 70 °C (dry environment)
Display
Illuminated dot-matrix
128 × 64 pixels
Display Units
Energy
Volume
Additional pulse inputs
Temperature
kWh, MWh, MJ, GJ, kBtu, MBtu, Mcal, Gcal
L, m
3
, gal (US), kgal (US), ft
3
(US)
Energy or volume
°C, °F
Lifespan Supply Modules
w/o supply
D battery
6 + 1 years (backup for metrological part)
12 + 1 years
Degree of Protection
IP Code
IP 65 in accordance to IEC 60529
Pulse Inputs
Frequencies
Without supply
D battery
External Mains
Input voltage
maximum 5 Hz
maximum 200 Hz
maximum 200 Hz
0 to 30 V
Pulse Outputs
Frequencies
Without supply
D battery
External Mains
Output voltage
maximum 5 Hz
maximum 200 Hz
maximum 200 Hz
0 to 60 V
Optical interface
Interface
according to IEC 62056-21:2002
NFC Interface
Interface
according to ISO/IEC 14443 Type A
M-Bus interface
Interface
Baud rate
Galvanic isolation
according to EN 13757-2/3
300 to 9600 baud
3.75 kV
Technical Data
Содержание Supercal 5 I
Страница 1: ...Instructions for Use Supercal 5 I...
Страница 6: ...6 Instruction for use Supercal 5...
Страница 55: ...55 Instruction for use Supercal 5 The interfaces of the NOWA adapter...
Страница 66: ......
Страница 67: ......
Страница 68: ...Sontex SA Rue de la Gare 27 CH 2605 Sonceboz Tel 41 32 488 30 00 sontex sontex ch www sontex ch 21 10...