SIP SonNet-Trend - Interface Range
49
Issue 1, Jun. 2014
To configure a Sensor module
48.
Select the
‘
OS
’ and press the ‘
Sensors
’ option to display the Sensor module configuration
page.
xv.
Locate
the ‘
Index
’ number corresponding to the ‘
Mod. num.
’ configured on the ‘
Map
points
’ page.
xvi.
Enter text (40 characters max) used to identify the associated parameter
in the ‘
Label
’
field. This is used to identify the parameter in the BeMS. It should be a concise
description of the parameter.
Caution
The ‘Label’ does not support ‘
\ / ( { ; , :
’ invalid characters.
xvii.
Inspect the
‘
Value
’ field. This displays the value recorded from the parameter
associated with the ‘
Module
’ number configured on the ‘
Map points
’ page.
xviii.
Enter the appropriate
engineering data value type in the ‘
Unit
’ field. This appears in the
BeMS and is used to identify the engineering data value, i.e. A (amps) if scaling a value
measuring a mA signal.