animeo KNX/EIB 4 AC MoCo · REF. 5050779 -
4/31
Slat position
0
All indications in the manual marked with * refers to the following terms:
Manual order
A manual order is a command generated by a local conventional switch or by a Somfy RTS radio hand transmitter.
A telegram received on the objects 0-7 is also understood as manual command.
Automatic order
A telegram received on the objects 8-15 is understood as an automatic order.
US switch ergonomics
With this parameter it is specified that the venetian blind is headed in US ergonomics over the local switch inputs or
over Somfy RTS radio hand transmitter.
Short manipulation of the switch (< 0.5 s): A move command is executed.
Long manipulation of the switch (> 0.5 s): A tilting command is executed as long as the switch is pressed. When re-
leasing the switch the tilting command is stopped. If the current position of the venetian blind is outside the tilting
time,a driving command is implemented with pressed button.
EU switch ergonomics
With this parameter it is specified that the venetian blind is headed in European Union ergonomics over the local switch
inputs or over Somfy RTS radio hand transmitter.
Short manipulation of the switch (< 0.5 s): A tilting step is implemented.
Long manipulation of the switch (> 0.5 s): A tilting command is implemented as long as the switch is pressed. If the
current position of the venetian blind is outside the tilting time, a driving command is executed.
Screen switch ergonomics
With this parameter it is specified that the end product is headed for screen ergonomics over the local switch inputs or
over Somfy RTS radio hand transmitter.
Short manipulation of the switch when the end product is in full swing: A stop command is executed.
Long manipulation when the end product is not in full swing: A driving command is executed.
m
This ergonomic is used to control screens, roller blinds, awnings and windows.
Definitions
INSIDE
OUTSIDE