animeo KNX/EIB 4 AC MoCo • REF. 5050779 -
20/31
Parameter cards „Binary input 1...4“
General information
For each binary input four different basic functions are available:
•
Venetian blind UP / DOWN
•
Switch/dry contact
•
8-Bit value (rising edge)
•
Dimming
The individual functions and parameters depend on the selection of the basic function and are now described. The four different possibilities
are described using screenshots of the binary input 1, contact A/B and are identical for the binary inputs 2-4, contacts C/D, E/F and G/H. The
default value of the basic function for the parameter cards binary input 1…4 is venetian blind, UP / DOWN.
n
When the basic function “Venetian blind, UP / DOWN” is selected please be certain about which contact controls the UP order and which
contact controls the DOWN order. The same attention is necessary when the basic function “Dimming” is selected. Please be certain about
which contact controls dimming brighter and which contact controls dimming darker.
Basic function
Options:
Venetian blind UP / DOWN
Switch/dry contact
8-Bit value (rising edge)
Dimming
Long operating (move) after
Options:
0,5 seconds
0,3....5,0 seconds
This parameter defines the operating time of the appropriate switch, which differentiates between sending a short-term telegram (step/stop)
and a long-term telegram (UP / DOWN motor). If the time is, for example, set to 0,5 seconds, only with a duration of application which is
generated longer than 0,5 seconds, a long-term telegram will be executed. With duration of an application which is smaller than 0,5
seconds a short-term telegram is generated.
Contact type input A
Options:
Normally open
Normally closed
Specified over this parameter is the contact type at the local input A. Normally open contact: The contact at the local input is not operated
open and operated closed. Normally closed contact: The contact at the local input is operated opened and not operated closed.
Contact type input B
Options:
Normally open
Normally closed
Specified over this parameter is the contact type at the local input B. Normally open contact: The contact at the local input is not operated
open and operated closed. Normally closed contact: The contact at the local input is operated opened and not operated closed.