PVI13KW Installation and Operation Manual
DOC-020028 rev 006
14
To disconnect the inverter from the building/utility grid, turn off the DC disconnect, then the AC
disconnect. Turn off the AC 3-phase building/utility breaker if needed.
Connection to dedicated 208V
AC, 45A 3-phase circuit. 8-2
AWG copper wire. Torque to
45-50 in- lb. (Shown without
plastic safety cover). If 480V
AC version, circuit should be
40A.
45A Fuses (for 208V AC
version), 600V, 45A AJT45
Solectria Renewables P/N ELC-
110110. (If 480V AC version,
use 40A fuses, AJT40, Solectria
Renewables P/N ELC-110102.)
AC Equipment Ground
connection 8-4 AWG copper
wire
Example customer/installer
knockout, connector & wires.
(3 –phases & ground).
Fig. 5 AC disconnect
(open showing connection)