background image

PVI13KW                                                                                   Installation and Operation Manual 

  

DOC-020028 rev 006

                  

34 

 
 
 

50

60

70

80

90

100

0.00

5.00

10.00

15.00

AC Power (kW AC)

Overall Efficiency DC (PV)  

to AC (3-phase) %

 

 

Fig. 13    PVI13KW peak efficiency plot at 320VDC input and 25C ambient temperature.

 

(peak efficiency values were measured with a 3% accurate power meter setup  and 

do not include any losses caused by long wires and transitory  

phenomena, i.e. MPP tracking) 

 
 
 

 

Содержание PVI 13KW

Страница 1: ...PVI13KW Installation and Operation Manual DOC 020028 rev 006 1 PVI13KW INSTALLATION AND OPERATION MANUAL Commercial Grid Tied Photovoltaic Inverter 2005 Solectria Renewables LLC Subject to Change ...

Страница 2: ...ation of the inverter the following safety symbols are used to indicate dangerous conditions and important safety instructions WARNING This indicates a fact or feature very important for the safety of the user and or which can cause a serious hardware damage if not applied appropriately Use extreme caution when performing this task NOTE This indicates a feature that is important either for optimal...

Страница 3: ...ewables contact information and authorized system installers Before installing or using the PVI13KW please read all instructions and caution markings in this manual and on the PVI13KW unit as well as the PV modules Connection of the PVI13KW to the electric utility grid must be done after receiving prior approval from the utility company and performed only by qualified personnel Completely cover th...

Страница 4: ...o Electrical Utility Grid 11 3 Commissioning the Inverter PV System 18 4 Power GFDI and Error LED Indicators 19 5 Troubleshooting Opening the Main Enclosure 22 6 Warranty Information and Liability 25 7 Technical Data 29 8 Appendices 35 Appendix A Product Datasheet 35 Appendix B Example String Sizing 37 Appendix C Contact Info and Authorized Distributors Dealers and Installers 40 Appendix D UL 1741...

Страница 5: ...tutional facility s electrical system which is connected to the electrical grid A 480V AC version is also available If the PV system and inverter are providing the same amount of electrical power that the facility is using then no power is taken from or fed into the utility grid If the facility is using more power than the PV system is providing then the utility grid provides the balance of power ...

Страница 6: ...spect the inverter thoroughly after it is delivered If any damage is seen please immediately notify the shipping company If there is any question about potential shipping damage contact Solectria Renewables A photo of the damage may be helpful Do not accept unit if visibly damaged or note visible damage when signing shipping company receipt Report damage immediately to shipping company Do not remo...

Страница 7: ...e inverter above the DC PV disconnect For optimal inverter life and performance do not mount the inverter in direct sunlight especially in hot climates although the inverter is designed to function at full power continuously in up to 45o C ambient temperatures In hot climates if the unit must be mounted in direct sunlight a metal sun shield is recommended It is recommended that the inverter is mou...

Страница 8: ... least a 2 open space behind it If wall mounted vertical 2 x 2 uni strut or channel can be used Air should be able to flow up behind the unit from below it to above it If you are installing the inverter in a utility vault or electrical closet the air circulation must be sufficient for heat dissipation provide external ventilation to maintain an ambient condition of less than 45 o C The ambient tem...

Страница 9: ...PVI13KW Installation and Operation Manual DOC 020028 rev 006 9 Fig 2 2a PVI13KW Mounting Diagram ...

Страница 10: ...also includes mounting tabs for wall mounting You can also use a combination of both mounting provisions For example 2 bolts in floor mount feet and 2 bolts in the wall mount tabs It is recommended to use galvanized grade 5 or better bolts or stainless steel bolts The correct bolt size is 3 8 10mm diameter If wall mounting is used be sure to verify sheer and pullout strength of anchors or other wa...

Страница 11: ...lt positions If a stand is used be sure inverter is securely mounted to stand the stand is adequately designed for the unit s weight and the stand is adequately attached to the floor wall or roof NOTE In the case of roof floor mounting temporary removal of disconnect doors may facilitate easy wiring of the unit only while wiring however only do so if necessary and acceptable by local codes and app...

Страница 12: ...onduit and Outlet Boxes UL514B are to be used For AC 3 phase wiring use 6 AWG recommended for the 208VAC version minimum 90o C 194o F copper wire for connection with the inverter s 3 phase AC disconnect 8 AWG recommended for the 480VAC version Torque terminal screws to 45 50 in lb Voltage drop and other considerations may dictate that larger wire sizes be used A maximum of 2 AWG copper conductor w...

Страница 13: ...the DC disconnect and wired using the manufacturer s directions This device gives important added protection from indirect lightning strikes and resulting surges that provide protection beyond the inverter s UL1741 requirements An additional arrestor can also be placed on the AC disconnect As with all PV systems a Grounding Electrode Conductor must be installed per UL690 47 and 250 166 This conduc...

Страница 14: ... AC 45A 3 phase circuit 8 2 AWG copper wire Torque to 45 50 in lb Shown without plastic safety cover If 480V AC version circuit should be 40A 45A Fuses for 208V AC version 600V 45A AJT45 Solectria Renewables P N ELC 110110 If 480V AC version use 40A fuses AJT40 Solectria Renewables P N ELC 110102 AC Equipment Ground connection 8 4 AWG copper wire Example customer installer knockout connector wires...

Страница 15: ...e to 35 in lb PV negative connections 4 2 AWG copper wire torque to 120 in lb PV positive connections 4 2 AWG copper wire torque to 120 in lb Example customer installer knockout connector wires 7 PV one PV feed ground It is best to run individual PV feeds for each PV string to avoid combining negatives at the array Customer installer wires not shown Fig 7 DC disconnect without Fused PV Combiner op...

Страница 16: ...AC equipment grounding conductor A 50A breaker is recommended for the dedicated PV system circuit breaker for the 208VAC version a 30A circuit breaker is recommended for the 480VAC version The grid impedance value at the connection point should be as low as possible to avoid an increase of the AC voltage to non permissible values while the inverter feeds to the grid Minimizing wiring impedance als...

Страница 17: ...be below 450V DC Vpv 450 V DC under all conditions as per NEC 690 7 Please read the Technical Info section and see PV string sizing table in Appendix B Inverter with fused PV combiner in DC disconnect enclosure There are 7 fuse blocks for up to 7 PV strings of 10 15A fuse rated PV module strings The positive wire from each string is connected to each fuse block bottom screw terminal There are also...

Страница 18: ...o check PV polarity once more simply by carefully using a 600V DC rated digital volt meter and probing the positive and negative PV connections in the disconnect enclosure Turning on the inverter Turn on the dedicated 3 phase circuit breaker on the building electrical panel Turn on the PVI13KW inverter s 3 phase AC disconnect Turn on the PVI13KW inverter s DC disconnect Watch the LED indicators fo...

Страница 19: ...for user interaction or maintenance The PVI13KW automatically starts back feeding 3 phase AC power into the grid every morning as the sun rises as soon as sufficient DC voltage and PV power is available The inverter DSP runs through various checks before going online with the grid and feeding power into the grid The LED indicators mounted on the right hand side of the enclosure just above the DC d...

Страница 20: ...8 View from right hand side of inverter above DC PV disconnect Description of LED symbols used to indicate LED status in this manual LED Off LED flashing 25 on 75 off LED on once per second LED on two times per second LED on with short interruptions 75 on 25 off LED on ...

Страница 21: ...nect breaker to be closed Is absent red green feeding grid normal daytime operation yellow MPP or constant voltage mode red green de rating mode reduction of power fed to the grid yellow due to increased temperature of red the heat sink green waiting for available DC power is too low yellow stronger sun red green ground fault ground fault of the PV panels yellow see chapter 5 red green GFDI fuse f...

Страница 22: ...ding hot module temperature MPP voltage and cold module temperature open circuit voltage OCV Contact installer or Solectria Renewables if malfunction persists If contacting Solectria Renewables for assistance please provide part number serial number short description of problem LED indicator status when problem started how often problem occurs under what conditions the problem occurs and informati...

Страница 23: ...ermined that the unit or any part of the unit should be shipped to Solectria Renewables for repair or replacement be sure to get an RMA from Solectria Renewables and use the same packing method as when it was shipped to you or request instruction on packing and or packing materials from Solectria Renewables to help insure a safe shipment Opening the Main Enclosure Normally the main enclosure or di...

Страница 24: ...uit DC disconnect PV connection with or without Fused PV Combiner GFDI Fuse 3A Night time off lining contactor NEMA 3 inverter enclosure with door open Filters Air exhaust out bottom Mounting feet Premium efficiency transformer MOV surge suppressors behind terminal block Fan relay Fan fuse 1A AC voltage sense fuses 0 1A Fig 9 Description and location of components ...

Страница 25: ...y Policy is stated below Solectria Renewables Warranty Coverage Solectria Renewables Limited Warranties are provided by Solectria Renewables LLC Solectria Renewables and cover defects in workmanship and materials Duration of a Solectria Renewables Warranty Period The warranty period is 60 months from the date of purchase of the PVI1800 PVI2500 PVI13kW or PVI60KW PVI77KW and PVI90KW by the end user...

Страница 26: ... extended warranty option has been purchased this extended warranty only applies to exposed outdoor locations defined as rooftop or open unprotected locations if the product has been purchased to include the gasket sealed AC and DC disconnect option or has a protective cover around 3 sides of inverter unit back and sides and over the top 4 60 away from back and top and 30 96 from sides Obtaining S...

Страница 27: ...S IN CONNECTION WITH YOUR SOLECTRIA RENEWABLES PRODUCT AND ARE WHERE PERMITTED BY LAW IN LIEU OF ALL OTHER WARRANTIES CONDITIONS GUARANTEES REPRESENTATIONS OBLIGATIONS AND LIABILITIES EXPRESS OR IMPLIED STATUTORY OR OTHERWISE IN CONNECTION WITH THE PRODUCT HOWEVER ARISING WHETHER BY CONTRACT TORT NEGLIGENCE PRINCIPLES OF MANUFACTURER S LIABILITY OPERATION OF LAW CONDUCT STATEMENT OR OTHERWISE INCL...

Страница 28: ... LOSSES DAMAGES COSTS OR EXPENSES WHETHER SPECIAL DIRECT INDIRECT CONSEQUENTIAL OR INCIDENTAL WHICH MIGHT ARISE OUT OF THE USE OF SUCH INFORMATION THE USE OF ANY SUCH INFORMATION WILL BE ENTIRELY AT THE USER S RISK WARNING LIMITATIONS ON USE Please refer to your product user manual for limitations on uses of the product Specifically please note that Solectria Renewables products are not intended f...

Страница 29: ...tact telephone number where you can be reached during work hours d A brief description of the problem Ship the unit prepaid to the address provided by your Solectria Renewables customer service representative Returning a product from outside of the USA or Canada In addition to the above you MUST include return freight funds and are fully responsible for all documents duties tariffs and deposits 7 ...

Страница 30: ...nd Operation Manual DOC 020028 rev 006 30 0 2 4 6 8 0 10 20 30 Voltage VDC DC Current A at 50 deg C at 20 deg C at 20 deg C Fig 10 Example representative PV module voltage current characteristic at various cell temperatures ...

Страница 31: ...ut power 14 kW DC inverter limited Maximum recommended 15 16 kW DC PV power modules STC DC disconnect for PV positive included Ground fault detection must detect 5A Ground fault interrupt 5A Output to AC grid connection The PVI13KW is designed to feed power into a standard 60Hz 3 phase 208V AC utility service or 208V AC provided within a facility by a step down transformer of not less than 15kVA A...

Страница 32: ...r UL1741 Ground fault protection 2005 NEC 690 5 2005 NEC 690 5 AC disconnect 3 phase included included Over current protection inverter limited inverter limited Short circuit protection per UL1741 per UL1741 Surge test per UL1741 per UL1741 Inverter peak Efficiency 94 50 100 load 94 50 100 load Other specifications DC combiner fuse enclosure 10A 15A fuses available Optional 7 pole NEMA 3R TVSS DC ...

Страница 33: ... 006 33 0 5 10 15 200 250 300 350 400 450 DC PV Voltage VDC AC Power kW Fig 11 Output power of PVI13KW 0 10 20 30 40 50 60 70 200 250 300 350 400 450 DC PV Input Voltage VDC DC Amperes ADC Fig 12 Maximum continuous DC current input for PVI13KW strike voltage ...

Страница 34: ... 00 AC Power kW AC Overall Efficiency DC PV to AC 3 phase Fig 13 PVI13KW peak efficiency plot at 320VDC input and 25C ambient temperature peak efficiency values were measured with a 3 accurate power meter setup and do not include any losses caused by long wires and transitory phenomena i e MPP tracking ...

Страница 35: ...PVI13KW Installation and Operation Manual DOC 020028 rev 006 35 Appendix A PVI13KW Data Sheet Link http www solren com downloads PVI_13KW pdf ...

Страница 36: ...PVI13KW Installation and Operation Manual DOC 020028 rev 006 36 ...

Страница 37: ... 20 VDC OCV extreme cold 25 VDC Power MPT 115 W Modules total in array 80 85 90 96 102 108 112 119 126 Modules per string 16 17 18 16 17 18 16 17 18 Strings in Parallel 5 5 5 6 6 6 7 7 7 Voltage MPT 264 280 5 297 264 280 5 297 264 280 5 297 OCV 25 deg C cells 320 340 360 320 340 360 320 340 360 OCV extreme cold 400 425 450 400 425 450 400 425 450 Power MPT STC 9200 9775 10350 11040 11730 12420 128...

Страница 38: ...MPT STC 7680 8960 10240 11520 12800 14080 15360 Inverter Used PVI13KW PVI13KW PVI13KW PVI13KW PVI13KW PVI13KW PVI13KW Module Manufacturer BP Solar Module Model BP 3160 24V module Voltage MPT 35 1 VDC Current MPT 4 55 ADC Current short circuit 4 8 ADC OCV 25 deg C cells 44 2 VDC OCV extreme cold 53 04 VDC Power MPT 160 W Modules total in array 48 56 64 72 80 88 96 Modules per string 8 8 8 8 8 8 8 S...

Страница 39: ... 2 VDC Current MPT 7 2 ADC Current short circuit 8 ADC OCV 25 deg C cells 28 9 VDC OCV extreme cold 34 68 VDC Power MPT 167 W Modules total in array 48 60 72 84 52 65 78 91 Modules per string 12 12 12 12 13 13 13 13 Strings in Parallel 4 5 6 7 4 5 6 7 Voltage MPT 278 4 278 4 278 4 278 4 301 6 301 6 301 6 301 6 OCV 25 deg C cells 346 8 346 8 346 8 346 8 375 7 375 7 375 7 375 7 OCV extreme cold 416 ...

Страница 40: ...Attn Paul Lyons P E 26 Glenwood Avenue Cambridge MA 02139 4708 Tel 617 868 1964 Fax 617 547 9140 www ZapotecEnergy com Borrego Solar Attn Mike Hall 2512 9th St Suite 6 Berkley CA 94710 Tel 510 843 1113 Fax 510 843 1116 www borregosolar com SolSource Energy Attn Jim Cahill 127 La Porte St Unit M Arcadia CA 91006 Tel 626 445 1410 Fax 626 445 1450 www solsourceenergy com The Alternative Energy Store ...

Страница 41: ...PVI13KW Installation and Operation Manual DOC 020028 rev 006 41 Appendix D ETL early use letter ...

Страница 42: ...PVI13KW Installation and Operation Manual DOC 020028 rev 006 42 ...

Отзывы: