PVI13KW Installation and Operation Manual
DOC-020028 rev 006
8
•
The cooling air exhausts at the bottom of the unit. Nothing should block the 2” clear space
under the enclosure defined by the 2” tall mounting feet.
•
A minimum distance of 10 inch (250mm) must be clear above the inverter for ventilation.
•
The inverter must be mounted with at least a 2” open space behind it. (If wall- mounted,
vertical, 2” x 2” uni-strut or channel can be used.) Air should be able to flow up behind the
unit from below it to above it.
•
If you are installing the inverter in a utility vault or electrical closet, the air circulation must
be sufficient for heat dissipation – provide external ventilation, to maintain an ambient
condition of less than 45
o
C. The ambient temperature should be kept as low as possible.
•
Correct mounting positions for the inverter: (side views)
Fig. 2.1
How to mount the inverter