Recommended Wiring Scheme
_____________________________________________________________________________________
4.
RECOMMENDED WIRING SCHEME
4.1
Mains and Control Description
Refer to drawing on page 11
Indication Description
Remarks
1L1, 3L2, 5L3
Connection to mains
voltage up to 600V
7K\ULVWRU¶V3,9UDWLQJLQWHUQDOFLUFXLWU\DQGLQVXODWLRQ
defines two voltage levels:
400V
for 208-400V +10%/ -15% 50/60Hz
600V
for 440-600V +10% /-15% 50/60Hz
2T1, 4T2, 6T3
Connection to motor
G
Connection to ground
For proper operation and for safety reasons soft RVS-
DXM must be properly grounded.
Terminal A2
Control phase
The control voltage operates the electronic circuitry
and the optional fans.
Terminal A1
Control neutral (return)
Two control voltages are available:
115
for 115V +10%/ -15% 50/60Hz
230
for 230V +10%/ -15% 50/60Hz
This voltage can be from a grounded or ungrounded
mains system.
Terminal B1
Input
±
START command.
Input from a N.O. contact.
To SOFT START the motor, close contact between A2
and B1.
To SOFT STOP the motor open contact between A2
and B1. If Deceleration time is set to a value other than
0 seconds the motor will soft stop.
If Deceleration time is set to 0 seconds the motor will
stop immediately. (Refer to section
7.6.5 on page 40).
If Aux Input is set as Start / Stop, then terminal B1 is
used as momentary N.O. Start input and input C1 is
used as maintained N.C Stop input. (Refer to section
7.6.9 on page 47)
For emergency stop of the motor disconnect control
voltage from A1, A2 terminals.
Note:
To reset a fault the START command must be
removed.
Terminal C1
Input
±
Auxiliary Input.
Input from a N.O. contact.
Input from a maintained contact, connected between
terminals A2 and C1 to operate as programmed input.
Aux. Input can be programmed as one of six options:
(1) Dual Adjust
(2) Generator Function
(3) Slow Speed / Reverse
(4) External fault
(5) Remote reset after fault has been
removed.
(6) Start / Stop. Terminal C1 can be used
as a maintained N.C Stop input and
terminal B1 as momentary N.O. Start
input.
For Aux. Input programming refer to section
7.6.9 on
page 47.
Terminal F1
&
Terminal F2
Fan control
An external jumper, connected between terminals F1
and F2 enables controlling the operation of the optional
fans. When F1 & F2 are connected the fans will
operate.
Caution
!!
These terminals carry 115VAC or 230VAC!