22
Installation
_____________________________________________________________________________________
6.
INSTALLATION
WARNING!
Do not interchange line and load connections
6.1
Prior to Installation
&KHFNWKDW0RWRU¶V)XOO/RDG$PSHUH)/$LVORZHUWKDQRUHTXDO
WRWKHVWDUWHU¶V)XOO/RDG&XUUHQW
)/&DQGWKDW0DLQVDQG&RQWUROYROWDJHVDUHDVLQGLFDWHGRQWKHVWDUWHU¶VVLGHODEHO
0DNHVXUH6WDUWHU¶V)/&
Motor FLA!
Make sure Mains voltage is right!
0DNHVXUH6WDUWHU¶V)/&
Motor FLA!
Make sure Control voltage is right!
RVS-DXM label - example
6.2
Mounting
The starter must be mounted vertically. Allow sufficient space (at least 100mm) above and below the
starter for suitable airflow.
It is recommended to mount the starter directly on the rear metal plate for better heat dissipation.
Note:
Do not mount the RVS-DXM directly on the rear metal plate in case a ventilation fan or ventilation
opening is on the back side of the RVS-DXM.
Do not mount the starter near heat sources.
Surrounding air temperature in the cabinet should not exceed 40ºC
Protect the starter from dust and corrosive atmospheres.
Note
: For harsh environments (sewage treatment plants, etc.), it is recommended to order the starter
with printed circuit board coating. Refer to section
3.3.6 on page 7 for ordering information.
6.2.1
Remote keypad installation
6.3
Temperature range & heat dissipation
The starter is rated to operate over a temperature range of -10ºC (14ºF) to + 40ºC (104ºF).
Relative non-condensed humidity inside the enclosure should not exceed 95%.