34
Control Keypad
_____________________________________________________________________________________
MAIN PARAMETERS
- **** -
Displays in MINIMIZED MODE and MAXIMIZED MODE
(Refer below for changing modes)
Display and default
values
Range Description
Remarks
UNDERVOLT. DELAY
5 SEC.
1
±
10sec. Sets
UNDERVOLT
TRIP DELAY.
Note
:
Becomes operational only after Start signal.
When voltage drops to zero (voltage outage) the
starter will trip immediately, overriding the delay.
OVERVOLT. TRIP
120 %
110-125% of
RATED
LINE VOLT.
Sets OVER
VOLTAGE
TRIP.
Trips the starter when mains voltage increases
above the set level for a time longer than
OVEERVOLT DELAY.
OVERVOLT. DELAY
2 SEC.
1
±
10sec. Sets
OVERVOLT
TRIP DELAY.
DISPLAY MODE
MINIMIZED
MINIMIZED/
MAXIMIZED
Sets Display
Mode
For operation convenience, there are two display
modes:
MINIMIZED
±
Display of pre-selected
parameters for standard applications.
MAXIMIZED
±
Display of all possible
parameters.
Setting Display Mode to MINIMIZED will
minimize the LCD displays. (Refer to section
7.4
7.6 on page 26 for more details)
PARAMETERS LOCK
NOT LOCKED
NOT
LOCKED/
LOCKED
Locks or
unlocks
parameter
modifications.
The software lock prevents undesired parameter
modification.
When locked, upon pressing
Store
,
ź
or
Ÿ
keys, the LCD displays:
UNAUTHORIZED ACCESS
STORE ENABLE
MAIN PARAMETERS
Storing
modified
parameters
To store selected parameters, press Store key.
Note
: Storing selected parameters is possible
only when
RAMP
LED does not lit.
Storing cannot be done when Soft Starting or
Soft Stopping.
When parameters have been correctly stored,
the LCD will read:
DATA SAVED OK
This concludes MAIN PARAMETER settings.
3UHVVLQJ6HOHFWNH\DIWHU³'$7$6$9('2.´
returns to the first display in this mode.
Note:
In case of a failure in parameter storing, the LCD
displays:
STORAGE ERROR
In this case Refer to section
9
±
³
TROUBLE
SHOOTING
´RQSDJH
61.