37
Control Keypad
________________________________________________________________________________________
START PARAMETERS
- **** -
Displays in MINIMIZED MODE and MAXIMIZED MODE
(refer to section
7.6.3 on page 32 for changing mode)
SETTING
as
described in
section
7.6.7
page 43.
Note:
When INITIAL VOLTAGE is set above
LW¶VPD[LPXPYDOXHGLVSOD\
changes to INITIAL CURRENT.
When INITIAL CURRENT is set, starter
causes current ramp instead of voltage
ramp.
CURRENT LIMIT
400% OF FLA
100-400%
Note:
Range can be
extended to
100-500% by
using the
WIDER
SETTING as
described in
section
7.6.7
page 43.
6HWVPRWRU¶V
highest current
during starting.
A too high setting will cause greater
current drawn from mains and faster
acceleration.
A setting that is too low may prevent
motor from completing acceleration
process and reaching full speed. In
general, this setting should be set to a
high enough value in order to prevent
stalling.
Note:
CURRENT LIMIT is not operating
during Run and Soft stop.
ACC. TIME
10 SEC.
1-30sec.
Note:
Range can be
Sets
ACCELERATION
TIME of the
'HWHUPLQHVPRWRU¶VYROWDJHUDPS
-up
time, from initial to full voltage.