42
Control Keypad
_____________________________________________________________________________________
7.6.6
Dual Adjustment Parameters
±
page 4
DUAL ADJUSTMENT
PARAMETERS
Displays in MAXIMIZED MODE only
(refer to section
7.6.3 on page 32 for changing mode)
Display and default
values
Description Remarks
When selecting GEN. START/STOP in mode I/O
PROGRAMMING PARAMETERS on page PROG.
INPUT C1 DUAL ADJUST (refer to section
7.6.9.1on
page 48) the following display appears:
D. ADJ: GENERATOR
PARAMETERS
DA: INIT. VOLT.
30%
6HWVPRWRU¶V,1,7,$/
STARTING
VOLTAGE
in DA
mode.
0RWRU¶V
torque
is directly
proportional to the
square of the voltage)
Refer to section
7.6.4 on page 36 parameter:
INITIAL VOLTAGE.
DA: INIT. CURRENT
100%
DA: CUR. LIMIT
400% OF FLA
6HWVPRWRU¶VKLJKHVW
current during starting
in DA mode.
Refer to section
7.6.4 on page 36 parameter:
CURRENT LIMIT.
DA: ACC. TIME
10 SEC.
Sets
ACCELERATION
TIME of the motor
in
DA mode.
Refer to section
7.6.4 on page 36 parameter:
ACC. TIME.
DA: DEC. TIME
0 SEC.
Sets
DECELERATION
TIME of the motor
in
DA mode.
Refer to section
7.6.5 on page 40 parameter:
DEC. TIME.
DA: MOTOR FLA
31 AMP.
6HWVPRWRU¶V)/$
(Full load Ampere)
in
DA mode.
Refer to section
7.6.3 on page 31 parameter:
MOTOR FLA.
STORE ENABLE
D. ADJ PARAMETERS
Same as STORE ENABLE MAIN PARAMETERS on
page 34.